Rockwell Automation Publication 1789-UM002K-EN-P - January 2015
47
Communicate with Devices on an Ethernet Network
Chapter 3
If you want the UDP option enabled, you should also enable the Gateway
functionality within RSLinx Gateway software. You must have RSLinx Gateway
software to enable Gateway functionality. Follow these steps.
1.
Launch RSLinx software on the computer with the controller.
2.
From the Communications menu, choose Configure Gateway.
The Configure RSLinx Gateway dialog box appears.
3.
Check Enable RSLinx Gateway.
4.
Click OK.
In many applications, initially leave UDP enabled so that you can configure
ControlNet and DeviceNet networks. After configuration is done, disable UDP
so the SoftLogix controller can have EtherNet/IP functionality. If you change the
UDP setting, you must restart RSLinx software for the change to take affect. To
restart RSLinx software, restart the computer.
For information on adding multiple Ethernet modules, see
.
Содержание SoftLogix 5800
Страница 1: ...SoftLogix 5800 System Catalog Numbers 1789 L10 1789 L30 1789 L60 User Manual...
Страница 4: ...4 Rockwell Automation Publication 1789 UM002K EN P January 2015 Summary of Changes Notes...
Страница 104: ...104 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 5 Configure and Use Simulated I O Notes...
Страница 110: ...110 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 6 Execute External Routines 9 Click OK...
Страница 148: ...148 Rockwell Automation Publication 1789 UM002K EN P January 2015 Chapter 7 Develop External Routines Notes...
Страница 256: ...256 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix E System Performance Tuning Guidelines Notes...
Страница 262: ...262 Rockwell Automation Publication 1789 UM002K EN P January 2015 Appendix G SoftLogix 5800 Revision History Notes...
Страница 270: ...270 Rockwell Automation Publication 1789 UM002K EN P January 2015 Index...
Страница 271: ......