Publication 1747-6.5.5 - August 2000
5-6
Communicating with DeviceNet from Another Network
The new driver will be added to the list of Configured Drivers in
RSLinx. (Your list will contain the drivers you have configured.)
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1747-SDN module via the
Ethernet network, you must configure the DeviceNet pass-through
driver (1747-SDNPT) using RSLinx, version 2.10 or higher. You must
also have configured the
Ethernet to PLC-5/SLC-5/5820-EI
driver as
described in the previous section and configured the SLC 5/05
processor’s Ethernet communications channel as described in
Appendix B
Perform the following steps:
1.
Start
RSLinx
.
2.
From the
Communications
menu, select
Configure Drivers
.
Содержание SLC 500 DeviceNet
Страница 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Страница 4: ......
Страница 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Страница 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Страница 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Страница 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Страница 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Страница 112: ...Publication 1747 6 5 5 August 2000 C 4 Configuring the Processor s RS 232 Port for the ControlNet Interface...
Страница 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Страница 124: ...Publication 1747 6 5 5 August 2000 F 6 Configuring the SLC 500 Processor s Communication Channels Using a DF1 Driver...
Страница 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Страница 137: ......
Страница 139: ...SLC500 DeviceNet Scanner Module User Manual...