Data Transfer File Instructions
Chapter 12
1217
Figure 12.15
FILETOWORD MOVE Format
FILE-TO-WORD MOVE
COUNTER ADDR: 030
POSITION: 001
FILE LENGTH: 001
FILE A: 110- 110
WORD ADDRESS: 010
030
(DN)
15
Numbers shown are default values. Bold numbers must be replaced by userentered values. The number of default address digits
initially displayed 3, 4, or 5 will depend on the size of the data table. Initially displayed default values are governed by the I/O rack
configuration.
COUNTER ADDRESS : Address of the instruction in the accumulated value area of the data table.
POSITION : Current word being operated upon (accumulated value of counter).
FILE LENGTH : Number of words in file (preset value of the counter).
FILE A : Starting address of source file.
WORD ADDRESS : Address of destination word outside the file.
Figure 12.16 shows the format of Figure 12.15 after the conditions listed
below have been entered:
COUNTER ADDR – 200
POSITION – 005
FILE LENGTH – 010
FILE A – starts at 474 and ends at 505
WORD ADDR – 400
The procedure for using the data monitor mode to enter and/or monitor file
data is presented in Section 12.5.