Introduction to Programming
Chapter 4
429
data has been entered using the data monitor mode. See Insert an
Instruction, above.
WARNING: When the [RECORD] key is pressed, the
substituted instruction is entered into memory immediately. If
the rung is true, the output instruction will be enabled and will
instantly energize the output device. Damage to equipment
and/or personal injury could result.
NOTE: Bit values and the data of word instructions are not cleared when
an instruction is replaced by another.
NOTE: If only the data of an instruction is to be changed, use the on-line
data change procedure described in Section 4.4.4.
Correct an Error
An error can be corrected during on-line programming any time before the
[RECORD] key is pressed using either of the following procedures:
Step 1 – Using the [
→
] and [
←
] cursor control keys, cursor back the digit
containing the error and correct it.
Step 2 – Press the [CANCEL COMMAND] key. It restores the ladder
diagram display and program logic to the original instruction and
address(es).
When inserting a rung, an error can be corrected before the output
instruction is entered (before the [RECORD] key is pressed) by either of
the following procedures:
Step 1 – Complete the rung by using an output energize instruction
addressed to an unused storage bit.
Step 2 – If the instruction being inserted is in error, press the [CANCEL
COMMAND] key to abort.
When either of these are done, proceed as follows:
Step 1 – Cursor to the instruction containing the error and correct it.
Step 2 – Enter the desired output instruction.
Step 3 – Verify that the inserted rung is correct.
Step 4 – Press the [RECORD] key.