Publication 2711P-UM001B-EN-P
Installing and Replacing Components
5-5
Installing/Replacing a
Communication Module
This section shows how to install and replace a Communication
Module on the PanelView Plus terminal. The Communication Module
installs over the Logic Module. The Communication Modules are
available as separate catalog numbers for specific communication
protocols. The installation is the same for all modules regardless of the
communication type.
Installation for 700 - 1500 Terminals
To install a Communication Module:
1.
Disconnect power from the terminal.
2.
If Display Module is removed from panel, set the module,
display side down, on a clean, flat, stable surface to prevent
scratches.
3.
Remove the label covering the Communication Module
connector on the Logic Module.
WARNING
!
If you connect or disconnect any communication
cable with power applied to this module or any
device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location
installations. Be sure that power is removed or the
area is nonhazardous before proceeding.
TIP
The Logic Module must be attached to the Display
Module before you attach the Communication
Module.
Logic Module
REMOVE LABEL TO INSTALL
COMMUNICATION MODULE
Содержание PanelView Plus 2711P
Страница 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Страница 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Страница 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Страница 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Страница 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Страница 169: ...AB Drives...