Applying Power
Chapter Objectives
This chapter provides information on:
•
wiring and safety guidelines
•
removing and installing power terminal block
•
connecting DC power
•
connecting AC power
•
resetting the terminal
•
startup sequence
Wiring and Safety
Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for
Employee Workplaces when wiring the PanelView Plus terminals. In
addition to the NFPA guidelines:
•
connect the terminal and other similar electronic equipment to
its own branch circuit.
•
protect the input power by a fuse or circuit breaker rated at no
more than 15 Amps.
•
route incoming power to the terminal by a separate path from
the communication lines.
•
where power and communication lines must cross, they should
cross at right angles.Communication lines can be installed in the
same conduit as low level DC I/O lines (less than 10 volts).
•
shield and ground cables appropriately to avoid Electromagnetic
Interference (EMI). Grounding minimizes noise from EMI and is
a safety measure in electrical installations.
For additional grounding recommendations, refer to the National
Electrical Code published by the National Fire Protection Association
of Boston.
Содержание PanelView Plus 2711P
Страница 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Страница 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Страница 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Страница 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Страница 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Страница 169: ...AB Drives...