1
Publication 2711P-UM001B-EN-P
Chapter
2
Installation
Chapter Objectives
This chapter provides instructions on how to install the PanelView
Plus terminals. It provides information on:
•
hazardous locations
•
environment
•
enclosures
•
clearances
•
required tools
•
cutout dimensions
•
mounting dimensions
•
400 - 600 panel installation
•
700 - 1500 panel installation
Hazardous Locations
This PanelView Plus terminals are suitable for use in:
•
Class I, Division 2, Groups A, B, C, D
•
Class II, Division 2, Groups F, G
•
Class III, Division 1
•
or non-hazardous locations
The following statement applies to use in hazardous locations.
Do not install the terminals in environments where atmospheric gases
have ignition temperatures
less
than 135 °C or 275 °F. In addition, the
PanelView Plus terminals have a temperature code of T4.
WARNING
!
Explosion Hazard
•
Substitution of components may impair suitability
for hazardous locations.
•
Do not disconnect equipment unless power has
been switched off and area is known to be
non-hazardous.
•
Do not connect or disconnect components unless
power has been switched off.
•
All wiring must comply with N.E.C. articles
501-4(b), 502-4(b), 503-3(b) as appropriate.
•
Peripheral equipment must be suitable for the
location it is used in.
Содержание PanelView Plus 2711P
Страница 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Страница 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Страница 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Страница 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Страница 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Страница 169: ...AB Drives...