
Publication 2711P-UM001B-EN-P
Troubleshooting and Maintenance
8-13
•
The following dialog appears if the Internal Compact Flash in
the PanelView Plus Logic Module is corrupt or invalid. This is a
fatal error
After pressing OK, you will be asked to power of the terminal
and insert a valid 6189-RWx Internal Compact Flash card.
Entering Configuration
Mode during Startup
If the PanelView Plus is configured to run an RSView ME .mer
application and you need to enter configuration mode, use the
following procedure.
To enter Configuration Mode during startup:
1.
On a Keypad terminal, hold down the Shift key.
On a Touch Screen terminal, tap the screen multiple times.
The following screen appears.
2.
Press the
Continue
button to access the Configuration Mode
screen.
If you are unable to enter configuration mode even after pressing the
Continue button, the firmware may be corrupted. Reload the
firmware. See page 7-1.
TIP
Begin pressing or tapping when the startup messages
have completed and when the first cursor appears.
Содержание PanelView Plus 2711P
Страница 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Страница 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Страница 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Страница 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Страница 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Страница 169: ...AB Drives...