Publication 1764-UM001A-US-P
3-10
Wiring Your Controller
Sinking and Sourcing
Circuits
Any of the MicroLogix 1500 DC embedded input groups can be configured as
sinking or sourcing depending on how the DC COM is wired on the group. See
pages 3-11 through 3-14 for sinking and sourcing wiring diagrams.
1764-24AWA Wiring Diagram
Input Terminals
Output Terminals
Type
Definition
Sinking Input
connection of a PNP sourcing device
The input energizes when high-level voltage is applied to
the input terminal (active high). Connect the power supply
VDC (-) to the DC COM terminal.
Sourcing Input
connection of an NPN sinking device
The input energizes when low-level voltage is applied to
the input terminal (active low). Connect the power supply
VDC (+) to the DC COM terminal.
IN 9
NOT
USED
IN 0
IN 2
AC
COM 1 IN 5
IN 7
IN 8
IN 10
NOT
USED
AC
COM 0
IN 1
IN 3
IN 4
IN 6
AC
COM 2
IN 11
L2 L1
L1
L2
“NOT USED” terminals are not intended for use as connection points.
120/240
VAC
OUT 10
OUT 8
OUT 7
OUT 5
VAC/
VDC 4
VAC/
VDC 3
VAC/
VDC 2
VAC/
VDC 1
VAC/
VDC 0
VAC
NEUT
OUT 11
OUT 9
VAC/
VDC 5
OUT 6
OUT 4
OUT 3
OUT 2
OUT 1
OUT 0
EARTH
GND
CR
CR
CR
CR
CR
CR
(Lo)
L2
(Hi)
L1
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...