![Allen-Bradley micrologix 1500 Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/allen-bradley/micrologix-1500/micrologix-1500_user-manual_2900209125.webp)
Publication 1764-UM001A-US-P
System Loading and Heat Dissipation
F-3
Validating System Loading - Examples
1764-24AWA and 1764-28BXB Base Units
1764-24BWA Base Units
Add any User 24V sensor current for applications with dc input sensors
(1764-24BWA base units only).
Loading Value
Total 5V dc Current Consumed
Total 24V dc Current Consumed
Total Watts
Maximum Current
2250 mA
400 mA
Calculated Current
650 mA + 670 mA = 1320 mA
120 mA + 250 mA = 370 mA
Maximum Power
16W
Calculated Power
1320 mA x 5V = 6.60W
+ 370 mA x 24V = 8.88W
= 15.48 W
User 24V Sensor Current Subtotal
(sum of all sensors must be 400 mA or less)
150 mA (example sensor value)
Loading Value
Total 5V dc Current
Consumed
Total 24V dc Current
Consumed
User 24V dc Sensor
Current Consumed
Total Watts
Maximum Current 2250 mA
400 mA
400 mA
Calculated Current
650 mA + 670 mA = 1320 mA
120 mA + 250 mA = 370 mA
150 mA
Maximum Power
22W
Calculated Power
1320 mA x 5V = 6.60W
+ 370 mA x 24V = 8.88W
+ 150 mA x 24V = 3.6W
= 19.08 W
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...