Publication 1764-UM001A-US-P
Understanding Communication Protocols
E-17
Modbus RTU Slave
Communication Protocol
(MicroLogix 1764-LSP
and 1764-LRP Series B
processors only)
Modbus RTU Slave is a Half-Duplex, master-slave communications protocol. The
Modbus network master initiates and controls all communications on the network.
Modbus protocol allows a single master to communicate with a maximum of 255
slave devices.
When a MicroLogix 1200 or 1500 Communications port is configured for
Modbus RTU Slave operation, the user must define where Modbus data (coils,
contacts, and registers) is mapped into the MicroLogix data space.
The Modbus address space is comprised of seven distinct memory ranges. Four of
these ranges can be mapped into MicroLogix data files. Three Modbus ranges are
fixed to MicroLogix file 2, the Status file. The table below illustrates Modbus to
MicroLogix mappings.
For more information on the MicroLogix 1500 configuration parameters for
Modbus Slave RTU (Remote Terminal Unit transmission mode) protocol, refer to
the MicroLogix 1200 and 1500 Programmable Controllers Instruction Set
Reference Manual, publication 1762-RM001A-US-P. For more information about
the Modbus Slave protocol, see the Modbus Protocol Specifications (available from
http://www.modicon.com/techpubs/).
Table E.5 Modbus to MicroLogix Memory Map
Modbus Addressing
Description
Valid MicroLogix Addressing
File Type
Data File Number Address
0001 to 4096
Read/Write Modbus Coil Data space
Bit (B) or Integer (N)
3 to 255
bits 0 to 4095
10001 to 14096
Read-Only Modbus Contact Data space
Bit (B) or Integer (N)
3 to 255
bits 0 to 4095
30001 to 30256
Read-Only Modbus Input Register space Bit (B) or Integer (N)
3 to 255
words 0 to 255
30501 to 30532
Modbus Communication Parameters
Communication Status
Files
2
words 0 to 31
31501 to 31566
Read-Only System Status File space
Status (S)
2
words 32 to 65
40001 to 40256
Read/Write Modbus Holding Register
space
Bit (B) or Integer (N)
3 to 255
words 0 to 255
41501 to 41566
Read/Write System Status File space
Status (S)
2
words 0 to 65
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...