Publication 1764-UM001A-US-P
F-2
System Loading and Heat Dissipation
MicroLogix 1500 System Expansion Worksheet - Example
The following
example
is provided to illustrate system expansion validation. The
table below accounts for the amount of 5V dc and 24V dc current consumed by
controller, expansion I/O, and user supplied equipment. The worksheet on the
next page shows how to validate your specific configuration. Current consumed by
the Base Units, Memory Modules, and Real Time Clock Modules has already been
factored into the calculations below.
NOTE
For an electronic version of the worksheet, visit the MicroLogix
web site. On the Internet, go to http://www.ab.com/micrologix.
Enter MicroLogix 1500; go to Tools and Tips, Expansion I/O
System Qualifier.
Catalog Number
Device Current Requirements
Current Consumed
at 5V dc (mA)
at 24V dc (mA)
at 5V dc (mA)
at 24V dc (mA)
1764-LSP
300
0
300
0
1764-LRP
380
0
1764-DAT
(1)
350
0
350
0
1761-NET-AIC
0
120
(2)
0
120
2707-MVH232 or 2707-MVP232
0
80
0
Subtotal: 650
120
Catalog Number
n
A
B
n x A
n x B
Number of Modules
(8 maximum)
Module Current Requirements
Calculated Current
at 5V dc (mA)
at 24V dc (mA)
at 5V dc (mA)
at 24V dc (mA)
1769-IA16
115
0
1769-IA8I
90
0
1769-IM12
100
0
1769-IQ16
1
115
0
115
0
1769-IQ6XOW4
1
105
50
105
50
1769-OA8
145
0
1769-OB16
1
200
0
200
0
1769-OV16
200
0
1769-OW8
2
125
100
250
200
1769-OW8I
125
100
1769-IF4
120
150
1769-OF2
120
200
Total Modules:
5
Subtotal: 670
250
(1) These are optional accessories. Current is consumed only if the accessory is installed.
(2) Current for the 1761-NET-AIC may be supplied from the controller communications port, as seen in this example, or from an external 24V dc source. No current is consumed
from the controller when an external source is used. The current for a 2707-MVH232 or 2707-MVP232 MicroView™ Operator Interface is supplied from the controller
communication port, if directly connected.
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...