DIR 1000587R0002 (Version 02)

2.6.  Putting into service and recommendations

2.6.1.  

Installation

Circuit-Breakers purchased with the trip unit assembled do not require this operation which is, however, necessary in the case 
of replacement.
Comply with the following instructions if the trip unit on the CB is replaced:
1.  With the circuit-breaker open and possibly isolated, connect the tip unit to the circuit-breaker itself by connecting all the 
cables as indicated in the assembly documents.
2.  Power the unit with 24V DC power supply or battery unit 140G-ELBU.
3.  If there are no other errors apart from the confi guration one, press the “i Test” button for a few seconds until all the red leds 
fl ash to confi rm that installation has taken place.
4.  Remove the battery unit.
5.  Power the trip unit by means of any supply source (Vaux, battery unit).
6.  Make sure that there are no confi guration errors (check that the LEDs are on in the Alive LED ON confi guration).
7.  The circuit-breaker and trip unit can now be put into service.

2.6.2. Connections

ATTENTION: Strict compliance with the wiring instructions given in this document is required.
This will ensure compliance with all the international reference standards and guarantee that the trip unit func-
tions perfectly even in heavy duty environmental and electromagnetic conditions. Pay particular attention to the 
earth connection.

2.6.3.  

CS and TC connection check

ATTENTION: If the LSIG has been installed by the user, remember to check (with the CB open and Vaux or battery 
unit), prior to putting the circuit-breaker into service, to make sure that the CS and TC cables have been con-
nected correctly. Make the correct connections if this is not the case. If all the red leds come on, it means that 
there is an error in the CS and/or TC connections

2.6.4. 

Connection of current sensor for external neutral

ATTENTION: Remember to set the InN in the appropriate way if the current sensor for the external neutral con-
ductor must be connected to a three-pole circuit-breaker.
During this phase, the circuit-breaker must be open and, if possible, isolated.

2.7. Default 

parameters

Prior to commissioning, adjust protection parameters according to specifi c application.
Rockwell Automation will apply the adhesive rating plates of all the variables concerning the CB (e.g. Type of CB, Rating Plug 
size, etc.) so as to provide the user with all the information needed to defi ne the parameters.

LSIG is supplied with the following default settings:

#

Protection

Threshold

Time

1

L

1 In

144 s

2

S

Off

0.1 s

3

I

4 In

--

4

G

Off

0.1 s

5

Mains frequency

50 Hz 

(1)

6

Neutral sel 

 

(2)

NOTES

:  

(1) =  50 Hz for IEC type CB
 

  60 Hz for UL type CB

(2) =  Off for three-pole CB
 

  50% for four-pole CB

Содержание LSIG

Страница 1: ...Die Ger te m ssen in einem passenden Geh use eingebaut und gegen Verschmutzung gesch tzt werden Avant le montage et la mise en service couper l alimentation secteur pour viter toute d charge Pr voir u...

Страница 2: ...u Area 20 3 5 2 1 Menu browsing 20 3 6 Protection functions 21 3 6 1 Notes about Protection Operation 21 3 6 2 Protection L 21 3 6 2 1 Thermal memory L 22 3 6 3 Protection S 22 3 6 3 1 Thermal memory...

Страница 3: ...ftware iTest Info test button on the front of the trip unit Trip CB opening generated by the trip unit OT Over Temperature 1 3 Safety Notes Read this manual carefully and completely use of the trip un...

Страница 4: ...gs Dip switches on the front allow the main protections and settings to be adjusted while the state of the trip unit is indicated by the leds of the front interface 2 2 1 Protections Symbol Protection...

Страница 5: ...condensation Degree of protection with LSIG installed in the circuit breaker IP 30 2 2 7 Electrical characteristics The trip unit is energized Directly by the internal current sensors connected to th...

Страница 6: ...d frequency and neutral protection 8 Rating Plug 9 iTest button 2 3 1 Dip switches The dip switches on the front of LSIG are used for adjusting the tripping thresholds of each protection and the tripp...

Страница 7: ...or 48 hours after switch off absence of internal or external power supply with the trip unit energized by battery unit alone and with the CB open it allows installation on the CB to be performed see p...

Страница 8: ...ime curve is given by the expression t s If the calculated value is less than t2 the real tripping time is forced to t2 t s t2 NOTES t s estimated tripping time If fault current given in In example 1...

Страница 9: ...xIn on the neutral 2 4 6 Protection against instantaneous short circuit Iinst Iinst is a software override protection The purpose of this protection is to maintain the integrity of the circuit breaker...

Страница 10: ...n 02 2 4 8 Trip curves The trip curves provided are merely for guidance and only show a sub group of the possible selections 2 4 8 1 Trip curves for functions L S t k I2 I t k I2 2 4 8 2 Trip curves f...

Страница 11: ...n 1 5 Earth fault current 0 05 4 In 0 3 4 In 1 5 2 5 2 Self monitoring LSIG provides certain self testing functions to facilitate failure analysis in the case of faulty operation or incorrect configur...

Страница 12: ...tions perfectly even in heavy duty environmental and electromagnetic conditions Pay particular attention to the earth connection 2 6 3 CS and TC connection check ATTENTION If the LSIG has been install...

Страница 13: ...but no trip occurs FN 6 Expected trip does not happen Function OFF FN enable protection function 7 LEDs irregularly turned on see par 2 3 2 8 Unexpected trip see par 2 3 2 9 L LED orange flashing FN...

Страница 14: ...l in accordance with the protection settings The state contacts of the CB provide information about the CB s position A graphic display and a set of push buttons allow all the information about the tr...

Страница 15: ...C 70 C Relative humidity 0 98 with condensation Degree of protection with trip unit installed in the CB IP 30 3 3 8 Electrical characteristics The trip unit is energized Directly by the internal curr...

Страница 16: ...FF No protection or delay alarm ON Flashing 1Hz Delay in progress for one or more of the following protections current L S G phase unbalance U Alarm for one or more Contact wear Temperature Connection...

Страница 17: ...f the last event that led to the trip unit being shut off function available within 48h from shut off ATTENTION When parameters whose adjustment includes a large number of options or values are edited...

Страница 18: ...flashes every 2 seconds The alarms are displayed in conjunction with an icon showing the type of alarm in question information active delay danger Icon Message Description Configuration Inconsistent p...

Страница 19: ...h the icons can be shown Starting from the position on the far right a description of the available icons is given below Position Icon Condition Description 1 OFF Separate 24V DC source is not present...

Страница 20: ...n each level by using the main push button panel ENTER to access a submenu or confirm an edited parameter ESC to quit a submenu or annul the changes made to a parameter UP and DOWN to scroll the menu...

Страница 21: ...is equipped with backup protection If the first command to the trip coil fails to open the circuit breaker immediately TC locked further trip commands are transmitted until the circuit breaker opens T...

Страница 22: ...ding on the situation in question ATTENTION The thermal memory function can only be activated if the standard type of curve has been selected t k I2 3 6 3 Protection S This protection can be disabled...

Страница 23: ...e same way as the protection S 3 6 6 Protection U Protection against current unbalance with a fixed time response can be disabled The breaker trips when for the t6 time setting or longer an unbalance...

Страница 24: ...f InN may be 50 100 200 With 140G N 1200 with Rating Plug at 800A Iu 1200A and I1 1In adjustment of InN may be 50 100 The I1 1In setting is the maximum setting of the protection against overload The r...

Страница 25: ...7 The best of the two data 10 or 40ms G 3 4 t k I2 0 1xIn I4 1xIn step 0 02xIn 0 2xIn I4 Start Up 1x I4 0 1s t4 1s step 0 05s minimum trip time If 4In 7 15 U t k 2 I6 90 step 1 0 5s t6 60s step 0 5s...

Страница 26: ...ection functions with the the same principle MM I 3 6 13 1 Trip curves for functions L S t k I2 I t s 10 1 10 2 1 10 102 103 104 10 3 1 10 100 10 1 x In 0 4 1 1 5 15 1 5 15 0 6 10 0 6 10 0 05 0 8 0 4...

Страница 27: ...in accordance with IEC 60255 121 type A t s 10 1 1 10 102 103 104 10 1 1 10 100 x In 3 144 0 4 1 0 4 1 L k 0 14 0 02 3 6 13 4 Trip curves for function L in accordance with IEC 60255 121 type B t s 10...

Страница 28: ...1000587R0002 Version 02 3 6 13 5 Trip curves for function L in accordance with IEC 60255 121 type C t s 10 1 1 10 102 103 104 1 10 100 10 1 x In 0 4 1 0 4 1 3 144 L k 80 2 3 6 13 6 Trip curves for fun...

Страница 29: ...power The main current measurements can be accessed by using the UP and DOWN buttons from the default page In the default page histograms with the currents appear on the display while the value and th...

Страница 30: ...he trips with a description of the event instead of the message about the protection and numbering that refers to the last event recorded Last Last 1 Last 2 LSIG MM are able to record up to 80 events...

Страница 31: ...ge 400 Vac Peak Vdc Maximum switching current 0 1 Aac Peak Adc Maximum switching power 40 W Contact Circuit insulation 1500 Vac ATTENTION Upon powering and if there is already energizing voltage on th...

Страница 32: ...CB Up to 5 options are available Name Description 1 CB status allows the user to view the CB state read by the trip unit 2 Auto Test allows the display and led test to be performed 3 Trip test allows...

Страница 33: ...LSIG MM unit from the circuit breaker 9 The remove the TC connector proceed as indicated in the figure alongside The uninstalling procedure is not strictly necessary for operation but is strongly reco...

Страница 34: ...to change the password and carefully define each edit able parameter before putting the trip unit into service LSIG MM are supplied with the following predefined parameters Protection On Off Threshol...

Страница 35: ...pply missing and the current is below the minimum value 2 Operating temperature out of range 1 See par 3 4 3 2 See par 3 3 7 and see par 3 6 7 7 Reading of I incorrect Current below the minimum thresh...

Страница 36: ...his situation may lead to personal injury or property damage 4 ACCESSORIES 4 1 External neutral This is a current sensor for the external neutral pole of the circuit breaker designed to provide neutra...

Страница 37: ...not belonging to Rockwell Automation are property of their respective companies Rockwell Automation maintains current product environmental compliance information on its website at http www rockwellau...

Отзывы: