DIR 1000587R0002 (Version 02)

3.12.  Troubleshooting

3.12.1. Troubleshooting

The following table lists a series of typical service conditions, to help you understand and solve hypothetical faults or malfunctions.

NOTES:

 

1.  Before consulting the following table, check for any error messages appearing for some seconds on the display.
2.  If the suggestions do not help in resolving the problem, please contact your Rockwell Automation technical support team.

Situation

Possible causes

Suggestions

1

The trip test cannot be run

1.  The busbar current is > 0
2.  The TC is not connected

1.  Verify current is not present to the trip 

unit

2.  Check the messages on the display

2

Trip times lower than 
expected

1.  Threshold is set too low
2.  Time is set too low
3.  Thermal memory enabled
4.  Incorrect Neutral Selection

1. Adjust 

threshold

2. Adjust 

time

3.  Exclude if not necessary
4.  Correct Neutral Selection

3

Trip times higher than 
expected

1.  Threshold is set too high
2.  Time is set too high
3. Curve 

I

2

t  inserted

4.  Incorrect Neutral Selection

1. Adjust 

threshold

2. Adjust 

time

3.  Exclude if not necessary
4.  Correct Neutral Selection

4

Rapid trip, with I3=Off

Current above I3 override value

Verify the cause of high current condition

5

High earth fault current, but 
no trip happens

1.  Incorrect selection of the sensor 
2.  Function G prevented with I>4In

1.  Set int. or ext. sensor
2.  Set function with I>4In

6

Display off

1.  24V DC supply missing and the current 

is below the minimum value.

2.  Operating temperature out of range

1.  See par. 3.4.3

2.  See par. 3.3.7 and see par. 3.6.7

7

Reading of I incorrect

Current below the minimum threshold that 
can be displayed

Verify current with a meter

8

Message “” instead of 
expected data

Function disabled or data off range

Verify protection function and settings

9

The expected trip does not 
occur

Trip function disabled

Enable trip if necessary

10

No activation of the 
Unbalance U protection

Values of I out of range

See par. 3.6.6

11

No display of trip data

24V DC supply

 missing, the buffer capacitor 

is discharged

See par. 1.7.2

12

The password is not 
requested

The password has been disabled

Re-enter the password with a value other 
than 0000

13

Impossible to change any 
parameter

LSIG-MM is activated

Parameter ara not adjustable when MM is 
activated

14

 Temp. sensor”  or 

 Start-up” message

Possible fault inside the trip unit

Contact Rockwell Automation Technical 
Support

15

Invalid date

1.  First installation
2.  Information lost due to power failure

Change date, see par. 3.9.4

16

Untimely trip

See par. 3.4.3.2

17

LED lighting

See par. 3.4.1

18

The language cannot be 
changed

1.  The trip unit is confi gured in the remote 

mode 

2.  CB not open
3. 

24V DC supply

 or battery unit not 

installed

1. Set 

locally

2. Open 

CB

3.   Power the trip unit

19

The activation contact of 
protection MM is not closed

Protection MM has not been enabled or 
K14/15 has no incoming signal

Check the menu to make sure that the 
protection is enabled and use a tester to 
check that voltage and polarity at the ends 
of K14 and K15 are correct

Содержание LSIG

Страница 1: ...Die Ger te m ssen in einem passenden Geh use eingebaut und gegen Verschmutzung gesch tzt werden Avant le montage et la mise en service couper l alimentation secteur pour viter toute d charge Pr voir u...

Страница 2: ...u Area 20 3 5 2 1 Menu browsing 20 3 6 Protection functions 21 3 6 1 Notes about Protection Operation 21 3 6 2 Protection L 21 3 6 2 1 Thermal memory L 22 3 6 3 Protection S 22 3 6 3 1 Thermal memory...

Страница 3: ...ftware iTest Info test button on the front of the trip unit Trip CB opening generated by the trip unit OT Over Temperature 1 3 Safety Notes Read this manual carefully and completely use of the trip un...

Страница 4: ...gs Dip switches on the front allow the main protections and settings to be adjusted while the state of the trip unit is indicated by the leds of the front interface 2 2 1 Protections Symbol Protection...

Страница 5: ...condensation Degree of protection with LSIG installed in the circuit breaker IP 30 2 2 7 Electrical characteristics The trip unit is energized Directly by the internal current sensors connected to th...

Страница 6: ...d frequency and neutral protection 8 Rating Plug 9 iTest button 2 3 1 Dip switches The dip switches on the front of LSIG are used for adjusting the tripping thresholds of each protection and the tripp...

Страница 7: ...or 48 hours after switch off absence of internal or external power supply with the trip unit energized by battery unit alone and with the CB open it allows installation on the CB to be performed see p...

Страница 8: ...ime curve is given by the expression t s If the calculated value is less than t2 the real tripping time is forced to t2 t s t2 NOTES t s estimated tripping time If fault current given in In example 1...

Страница 9: ...xIn on the neutral 2 4 6 Protection against instantaneous short circuit Iinst Iinst is a software override protection The purpose of this protection is to maintain the integrity of the circuit breaker...

Страница 10: ...n 02 2 4 8 Trip curves The trip curves provided are merely for guidance and only show a sub group of the possible selections 2 4 8 1 Trip curves for functions L S t k I2 I t k I2 2 4 8 2 Trip curves f...

Страница 11: ...n 1 5 Earth fault current 0 05 4 In 0 3 4 In 1 5 2 5 2 Self monitoring LSIG provides certain self testing functions to facilitate failure analysis in the case of faulty operation or incorrect configur...

Страница 12: ...tions perfectly even in heavy duty environmental and electromagnetic conditions Pay particular attention to the earth connection 2 6 3 CS and TC connection check ATTENTION If the LSIG has been install...

Страница 13: ...but no trip occurs FN 6 Expected trip does not happen Function OFF FN enable protection function 7 LEDs irregularly turned on see par 2 3 2 8 Unexpected trip see par 2 3 2 9 L LED orange flashing FN...

Страница 14: ...l in accordance with the protection settings The state contacts of the CB provide information about the CB s position A graphic display and a set of push buttons allow all the information about the tr...

Страница 15: ...C 70 C Relative humidity 0 98 with condensation Degree of protection with trip unit installed in the CB IP 30 3 3 8 Electrical characteristics The trip unit is energized Directly by the internal curr...

Страница 16: ...FF No protection or delay alarm ON Flashing 1Hz Delay in progress for one or more of the following protections current L S G phase unbalance U Alarm for one or more Contact wear Temperature Connection...

Страница 17: ...f the last event that led to the trip unit being shut off function available within 48h from shut off ATTENTION When parameters whose adjustment includes a large number of options or values are edited...

Страница 18: ...flashes every 2 seconds The alarms are displayed in conjunction with an icon showing the type of alarm in question information active delay danger Icon Message Description Configuration Inconsistent p...

Страница 19: ...h the icons can be shown Starting from the position on the far right a description of the available icons is given below Position Icon Condition Description 1 OFF Separate 24V DC source is not present...

Страница 20: ...n each level by using the main push button panel ENTER to access a submenu or confirm an edited parameter ESC to quit a submenu or annul the changes made to a parameter UP and DOWN to scroll the menu...

Страница 21: ...is equipped with backup protection If the first command to the trip coil fails to open the circuit breaker immediately TC locked further trip commands are transmitted until the circuit breaker opens T...

Страница 22: ...ding on the situation in question ATTENTION The thermal memory function can only be activated if the standard type of curve has been selected t k I2 3 6 3 Protection S This protection can be disabled...

Страница 23: ...e same way as the protection S 3 6 6 Protection U Protection against current unbalance with a fixed time response can be disabled The breaker trips when for the t6 time setting or longer an unbalance...

Страница 24: ...f InN may be 50 100 200 With 140G N 1200 with Rating Plug at 800A Iu 1200A and I1 1In adjustment of InN may be 50 100 The I1 1In setting is the maximum setting of the protection against overload The r...

Страница 25: ...7 The best of the two data 10 or 40ms G 3 4 t k I2 0 1xIn I4 1xIn step 0 02xIn 0 2xIn I4 Start Up 1x I4 0 1s t4 1s step 0 05s minimum trip time If 4In 7 15 U t k 2 I6 90 step 1 0 5s t6 60s step 0 5s...

Страница 26: ...ection functions with the the same principle MM I 3 6 13 1 Trip curves for functions L S t k I2 I t s 10 1 10 2 1 10 102 103 104 10 3 1 10 100 10 1 x In 0 4 1 1 5 15 1 5 15 0 6 10 0 6 10 0 05 0 8 0 4...

Страница 27: ...in accordance with IEC 60255 121 type A t s 10 1 1 10 102 103 104 10 1 1 10 100 x In 3 144 0 4 1 0 4 1 L k 0 14 0 02 3 6 13 4 Trip curves for function L in accordance with IEC 60255 121 type B t s 10...

Страница 28: ...1000587R0002 Version 02 3 6 13 5 Trip curves for function L in accordance with IEC 60255 121 type C t s 10 1 1 10 102 103 104 1 10 100 10 1 x In 0 4 1 0 4 1 3 144 L k 80 2 3 6 13 6 Trip curves for fun...

Страница 29: ...power The main current measurements can be accessed by using the UP and DOWN buttons from the default page In the default page histograms with the currents appear on the display while the value and th...

Страница 30: ...he trips with a description of the event instead of the message about the protection and numbering that refers to the last event recorded Last Last 1 Last 2 LSIG MM are able to record up to 80 events...

Страница 31: ...ge 400 Vac Peak Vdc Maximum switching current 0 1 Aac Peak Adc Maximum switching power 40 W Contact Circuit insulation 1500 Vac ATTENTION Upon powering and if there is already energizing voltage on th...

Страница 32: ...CB Up to 5 options are available Name Description 1 CB status allows the user to view the CB state read by the trip unit 2 Auto Test allows the display and led test to be performed 3 Trip test allows...

Страница 33: ...LSIG MM unit from the circuit breaker 9 The remove the TC connector proceed as indicated in the figure alongside The uninstalling procedure is not strictly necessary for operation but is strongly reco...

Страница 34: ...to change the password and carefully define each edit able parameter before putting the trip unit into service LSIG MM are supplied with the following predefined parameters Protection On Off Threshol...

Страница 35: ...pply missing and the current is below the minimum value 2 Operating temperature out of range 1 See par 3 4 3 2 See par 3 3 7 and see par 3 6 7 7 Reading of I incorrect Current below the minimum thresh...

Страница 36: ...his situation may lead to personal injury or property damage 4 ACCESSORIES 4 1 External neutral This is a current sensor for the external neutral pole of the circuit breaker designed to provide neutra...

Страница 37: ...not belonging to Rockwell Automation are property of their respective companies Rockwell Automation maintains current product environmental compliance information on its website at http www rockwellau...

Отзывы: