background image

(36)

DIR 1000587R0002 (Version 02)

3.12.2. 

In the case of a fault

ATTENTION:  If you suspect that the trip unit is faulty, functions incorrectly or has generated an unwanted trip, 
you are strongly advised to strictly comply with the following instructions in 
Measurements menu 

 Historicals 

 Trip:

1.  Make a note of the type of protection that has tripped by accessing the LAST TRIP page if there is an external power supply 

(24V DC supply or battery) or by pressing “i Test” if in self-powering mode.

2.  Record the type of circuit-breaker, number of poles, any accessories connected, In, Serial Number (see par. 14.4) and the SW 

version.

3.  Prepare a brief description of the opening  (what LEDs and/or indications were displayed? when did it happen?, how many 

times ?, was it always under the same conditions? what type of load? what voltage? what current? is the event reproducible?)

4.   Send/communicate all the information collected, together with the circuit diagram for the circuit-breaker, to your nearest AB 

Customer Support service.

The completeness and accuracy of the information given to the Rockwell Auotmation Technical Support will facilitate technical 
analysis of the problem encountered, and will allow us to carry out all actions useful for the user rapidly. 

ATTENTION:  Letting a switch run with a fault that has not been remedied may lead to an apparatus malfunction 
or shutdown. Remove the apparatus immediately until it can be inspected or repaired. This situation may lead 
to personal injury or property damage.

4.  

ACCESSORIES

4.1.  

External neutral

This is a current sensor for the external neutral pole of the circuit-breaker, designed to provide neutral protection for three-pole 
circuit-breakers. Further details about connection of the external neutral are available in document 1000529R0513.

4.2. Rating 

Plug

The rating plug defi nes the rated current In, which is essential for regulating the protections. This is because the 
regulation of all the protections refers to In (e.g.: I1= 0.4 xIn).
The rating plug is installed in the trip unit, on a dedicated front connector and is available to the user. 
The trip unit can be equipped with various different Rating Plug models, up to value Iu (uninterrupted rated cur-
rent Iu of the CB given on the rating plate of the front guard).
Example: CB 140G-N 800 has Iu= 800 A, and can be fi tted with a rating plug with In

 800A.

The module is interchangeable, with the trip unit off and the CB open.

The trip unit continuously checks for the presence of the rating plug and signals its absence or any assembly errors.

ATTENTION: Replacement of the rating plug with the trip unit on or the CB closed could lead to faulty trip unit 
operation or undesired opening of the CB

.

4.3.  Battery Unit (140G-ELBU)

Battery unit is an external unit allowing the trip unit to be energized so that Installation, Autotest and Trip Test 
can be performed, along with verifi cations with the CB open. The unit is connected to the trip unit by means of 
the front service connector.

 

At the end of its life, this equipment should be collected separately from any unsorted municipal waste

Содержание LSIG

Страница 1: ...Die Ger te m ssen in einem passenden Geh use eingebaut und gegen Verschmutzung gesch tzt werden Avant le montage et la mise en service couper l alimentation secteur pour viter toute d charge Pr voir u...

Страница 2: ...u Area 20 3 5 2 1 Menu browsing 20 3 6 Protection functions 21 3 6 1 Notes about Protection Operation 21 3 6 2 Protection L 21 3 6 2 1 Thermal memory L 22 3 6 3 Protection S 22 3 6 3 1 Thermal memory...

Страница 3: ...ftware iTest Info test button on the front of the trip unit Trip CB opening generated by the trip unit OT Over Temperature 1 3 Safety Notes Read this manual carefully and completely use of the trip un...

Страница 4: ...gs Dip switches on the front allow the main protections and settings to be adjusted while the state of the trip unit is indicated by the leds of the front interface 2 2 1 Protections Symbol Protection...

Страница 5: ...condensation Degree of protection with LSIG installed in the circuit breaker IP 30 2 2 7 Electrical characteristics The trip unit is energized Directly by the internal current sensors connected to th...

Страница 6: ...d frequency and neutral protection 8 Rating Plug 9 iTest button 2 3 1 Dip switches The dip switches on the front of LSIG are used for adjusting the tripping thresholds of each protection and the tripp...

Страница 7: ...or 48 hours after switch off absence of internal or external power supply with the trip unit energized by battery unit alone and with the CB open it allows installation on the CB to be performed see p...

Страница 8: ...ime curve is given by the expression t s If the calculated value is less than t2 the real tripping time is forced to t2 t s t2 NOTES t s estimated tripping time If fault current given in In example 1...

Страница 9: ...xIn on the neutral 2 4 6 Protection against instantaneous short circuit Iinst Iinst is a software override protection The purpose of this protection is to maintain the integrity of the circuit breaker...

Страница 10: ...n 02 2 4 8 Trip curves The trip curves provided are merely for guidance and only show a sub group of the possible selections 2 4 8 1 Trip curves for functions L S t k I2 I t k I2 2 4 8 2 Trip curves f...

Страница 11: ...n 1 5 Earth fault current 0 05 4 In 0 3 4 In 1 5 2 5 2 Self monitoring LSIG provides certain self testing functions to facilitate failure analysis in the case of faulty operation or incorrect configur...

Страница 12: ...tions perfectly even in heavy duty environmental and electromagnetic conditions Pay particular attention to the earth connection 2 6 3 CS and TC connection check ATTENTION If the LSIG has been install...

Страница 13: ...but no trip occurs FN 6 Expected trip does not happen Function OFF FN enable protection function 7 LEDs irregularly turned on see par 2 3 2 8 Unexpected trip see par 2 3 2 9 L LED orange flashing FN...

Страница 14: ...l in accordance with the protection settings The state contacts of the CB provide information about the CB s position A graphic display and a set of push buttons allow all the information about the tr...

Страница 15: ...C 70 C Relative humidity 0 98 with condensation Degree of protection with trip unit installed in the CB IP 30 3 3 8 Electrical characteristics The trip unit is energized Directly by the internal curr...

Страница 16: ...FF No protection or delay alarm ON Flashing 1Hz Delay in progress for one or more of the following protections current L S G phase unbalance U Alarm for one or more Contact wear Temperature Connection...

Страница 17: ...f the last event that led to the trip unit being shut off function available within 48h from shut off ATTENTION When parameters whose adjustment includes a large number of options or values are edited...

Страница 18: ...flashes every 2 seconds The alarms are displayed in conjunction with an icon showing the type of alarm in question information active delay danger Icon Message Description Configuration Inconsistent p...

Страница 19: ...h the icons can be shown Starting from the position on the far right a description of the available icons is given below Position Icon Condition Description 1 OFF Separate 24V DC source is not present...

Страница 20: ...n each level by using the main push button panel ENTER to access a submenu or confirm an edited parameter ESC to quit a submenu or annul the changes made to a parameter UP and DOWN to scroll the menu...

Страница 21: ...is equipped with backup protection If the first command to the trip coil fails to open the circuit breaker immediately TC locked further trip commands are transmitted until the circuit breaker opens T...

Страница 22: ...ding on the situation in question ATTENTION The thermal memory function can only be activated if the standard type of curve has been selected t k I2 3 6 3 Protection S This protection can be disabled...

Страница 23: ...e same way as the protection S 3 6 6 Protection U Protection against current unbalance with a fixed time response can be disabled The breaker trips when for the t6 time setting or longer an unbalance...

Страница 24: ...f InN may be 50 100 200 With 140G N 1200 with Rating Plug at 800A Iu 1200A and I1 1In adjustment of InN may be 50 100 The I1 1In setting is the maximum setting of the protection against overload The r...

Страница 25: ...7 The best of the two data 10 or 40ms G 3 4 t k I2 0 1xIn I4 1xIn step 0 02xIn 0 2xIn I4 Start Up 1x I4 0 1s t4 1s step 0 05s minimum trip time If 4In 7 15 U t k 2 I6 90 step 1 0 5s t6 60s step 0 5s...

Страница 26: ...ection functions with the the same principle MM I 3 6 13 1 Trip curves for functions L S t k I2 I t s 10 1 10 2 1 10 102 103 104 10 3 1 10 100 10 1 x In 0 4 1 1 5 15 1 5 15 0 6 10 0 6 10 0 05 0 8 0 4...

Страница 27: ...in accordance with IEC 60255 121 type A t s 10 1 1 10 102 103 104 10 1 1 10 100 x In 3 144 0 4 1 0 4 1 L k 0 14 0 02 3 6 13 4 Trip curves for function L in accordance with IEC 60255 121 type B t s 10...

Страница 28: ...1000587R0002 Version 02 3 6 13 5 Trip curves for function L in accordance with IEC 60255 121 type C t s 10 1 1 10 102 103 104 1 10 100 10 1 x In 0 4 1 0 4 1 3 144 L k 80 2 3 6 13 6 Trip curves for fun...

Страница 29: ...power The main current measurements can be accessed by using the UP and DOWN buttons from the default page In the default page histograms with the currents appear on the display while the value and th...

Страница 30: ...he trips with a description of the event instead of the message about the protection and numbering that refers to the last event recorded Last Last 1 Last 2 LSIG MM are able to record up to 80 events...

Страница 31: ...ge 400 Vac Peak Vdc Maximum switching current 0 1 Aac Peak Adc Maximum switching power 40 W Contact Circuit insulation 1500 Vac ATTENTION Upon powering and if there is already energizing voltage on th...

Страница 32: ...CB Up to 5 options are available Name Description 1 CB status allows the user to view the CB state read by the trip unit 2 Auto Test allows the display and led test to be performed 3 Trip test allows...

Страница 33: ...LSIG MM unit from the circuit breaker 9 The remove the TC connector proceed as indicated in the figure alongside The uninstalling procedure is not strictly necessary for operation but is strongly reco...

Страница 34: ...to change the password and carefully define each edit able parameter before putting the trip unit into service LSIG MM are supplied with the following predefined parameters Protection On Off Threshol...

Страница 35: ...pply missing and the current is below the minimum value 2 Operating temperature out of range 1 See par 3 4 3 2 See par 3 3 7 and see par 3 6 7 7 Reading of I incorrect Current below the minimum thresh...

Страница 36: ...his situation may lead to personal injury or property damage 4 ACCESSORIES 4 1 External neutral This is a current sensor for the external neutral pole of the circuit breaker designed to provide neutra...

Страница 37: ...not belonging to Rockwell Automation are property of their respective companies Rockwell Automation maintains current product environmental compliance information on its website at http www rockwellau...

Отзывы: