70
Rockwell Automation Publication 842E-UM001C-EN-P - September 2016
Chapter 7
Diagnostics and Troubleshooting
The following error messages stem from the RSLogix 5000® software.
2
16
Position error
LY digital random error and LY MFP5 error
(single position)
17
Position error
Position multi-turn error, synchronization
18
Position error
Position multi-turn error, synchronization
(quad-single)
19
Position error
Position multi-turn error, internal interface
20
Position error
Position multi-turn error FRAM (magnitude)
21
Reserved
Always 0
22
Reserved
23
Reserved
3
24
Position or memory error
Memory or EEPROM Check Sum error
25
Memory error
Memory or EEPROM I2C error
26
Start-up error
Start-up error
27
Diagnostic error
This flag is set if the encoder detects a
diagnostic error.
28
Reserved
29
Sanity-check flag
This flag is set if the encoder detects a
diagnostic error.
30
Slave sign of life
This functionality is active if byte 0 of attribute
106 is set.
31
Reserved
Error Code
Message
Possible Cause
16#0108
Connection-request error
connection type (multi-cast/uni-
cast) not supported.
Check whether the configuration assembly (instance 100 of
the Assembly Object) is activated. If yes, check whether the
configuration data are correctly and fully configured in this
assembly (see Figure xx on page 55).
16#0114
Electronic keying mismatched:
electronic keying product code
and/or vendor ID mismatched.
Check whether the wrong EDS file has been selected (for
example, single-turn instead of multi-turn or vice versa).
16#0127
Connection request error: invalid
output size.
Check whether the correct communication format for the
control system is used. The default value in the control system
is “Data-DINT.” The encoder requires the communication
format: “Input Data-DINT.”
16#0204
Connection request error:
connection time-out.
Check the supply voltage on the encoder.
Check the Ethernet cables for the encoder for open circuit.
Check whether the IP address of the encoder matches the IP
address that is saved in the control system. Possible causes:
• The address switches are not engaged correctly.
• The encoder has lost the IP address that is assigned to it
after switching back on.
Table 4 - Error Messages
Fault
Header
[byte]
Bit
Name
Description
Table 3 - Sensor Error Table
Содержание EtherNet/IP 842E-MIP10BA
Страница 6: ...6 Rockwell Automation Publication 842E UM001C EN P September 2016 Table of Contents Notes...
Страница 8: ...8 Rockwell Automation Publication 842E UM001C EN P September 2016 Preface Notes...
Страница 44: ...44 Rockwell Automation Publication 842E UM001C EN P September 2016 Chapter 4 Installation Notes...
Страница 95: ...Rockwell Automation Publication 842E UM001C EN P September 2016 95 RSLogix 5000 Sample Code Appendix B Notes...