Rockwell Automation Publication 842E-UM001C-EN-P - September 2016
37
EtherNet/IP Overview
Chapter 3
106
6A
Set
NV
Slave sign of life
DINT
Flags for encoder functionalities
(Bit field):
Bit 0: Slave sign of life (on/off)
Bit 1…7: not used
Bit 8…15: UpdateFactor (1…127)
Bit 16…31: not used
0x0000500
107
6B
Get
NV
Encoder motion time
DINT
Storage of the motion time. This
counter is incrementing if the encoder
is in rotation [sec].
0
108
6C
Get
NV
Encoder operating time [second] DINT
Storage of the operating time. This
counter is incrementing if the encoder
is powered on [sec].
0
109
6D
Get
NV
Max velocity
RA [cnts/ms]
DINT
Storage of the maximum velocity of
the encoder in operational state.
0
110
6E
Get
NV
Max acceleration [cnts/(ms)2]
DINT
Storage of the maximum acceleration
of the encoder in operational state.
0
111
6F
Get
NV
Max temp [°C/100]
DINT
Storage of the maximum temperature
of the encoder in operational state
2000
112
70
Get
NV
Min temp [°C/100]
DINT
Storage of the minimum temperature
of the encoder in operational state
2000
113
71
Get
NV
Number of startups
DINT
Storage of the number of startups
(power-on) cycles
0
114
72
Get
V
light-emitting diode current
value [µA]
INT
Current light-emitting diode current
[µA]
Range: 200…25.000
200…25.000
(0)
115
73
Get
NV
Max current value [µA]
INT
Max. light-emitting diode current [µA] 1.500
116
74
Get
NV
Min current value [µA]
INT
Min. light-emitting diode current [µA] 1.500
117
0X75
Get
V
Direction change counter
UDINT
Direction change counter, this counter
is incrementing if the encoder is
changing the direction, for example,
cw to ccw or ccw to cw.
0
118
0x76
Get
V
Rotation counter-forward
UDINT
Rotation counter (0) (forward
counter), this counter increments if the
encoder was moving from standstill to
a positive direction (cw).
0
119
0x77
Get
V
Rotation counter-backwards
UDINT
Rotation counter (1) (backwards
counter), this counter increments if the
encoder was moving from standstill to
a negative direction (ccw).
0
120
0x78
Get
V
Power supply voltage (mV)
UINT
Current supply voltage (mV)
Range: 9.500…30.500
9,500
30,500
(24,000)
121
0x79
Get
V
Maximum power supply voltage
(V)
UINT
Maximum power supply voltage, this
value is stored to the EEPROM data.
0
33
(0)
122
0x7A
Get
V
Preset offset value
DINT
Vendor-specific attribute:
Offset value is calculated when using
the preset function.
(00000000)
125
0x7D
Set
NV
Endless shaft functionality
BOOL
Encoder scaling with endless shaft
(only with a multi-turn). 0: OFF,
1: ON
(0)
126
0x7E
Set
NV
Number of rotations, nominator UDINT
This parameter is used if the parameter
“endless shaft functionality” is set
(1:ON)
1
2,048
(2,048)
Attribute ID
(dec)
Attribute ID
(hex)
Access
rule
(1)
NV /
V
(2)
Name
Data type Description
Min. / Max.
(default)
Table 17 - Instance Attributes of the Position Sensor Object
Содержание EtherNet/IP 842E-MIP10BA
Страница 6: ...6 Rockwell Automation Publication 842E UM001C EN P September 2016 Table of Contents Notes...
Страница 8: ...8 Rockwell Automation Publication 842E UM001C EN P September 2016 Preface Notes...
Страница 44: ...44 Rockwell Automation Publication 842E UM001C EN P September 2016 Chapter 4 Installation Notes...
Страница 95: ...Rockwell Automation Publication 842E UM001C EN P September 2016 95 RSLogix 5000 Sample Code Appendix B Notes...