Publication 1756-UM050A-EN-P - December 2001
6-12
Using Analog I/O with Direct Connection
Test the Example
Application
Use the following procedure to test the operation of the remote
analog output:
1.
Connect a voltmeter across the channel 0 output of the 1756-OF8
analog output module as shown in the following figure:
2.
Restore
RSLogix5000
and place the controller in
Run
mode.
3.
Measure the output voltage of channel 0. You should see it slowly
rise to approximately 10V, reset to zero, start rising again, etc.
This completes the Direct Connect I/O example.
What’s Next?
The following chapter describes an example application in which one
controller sends a message to another controller using produced and
consumed tags.
TIP
Refer to the
ControlLogix Analog I/O Module User
Manual
, publication 1756-6.5.9, for assistance in
wiring and debugging the I/O modules.
VOUT-0
RTN
1
5
1756-OF8
V
+
–
Содержание ControlLogix 1756-ENBT
Страница 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Страница 4: ......
Страница 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Страница 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Страница 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Страница 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Страница 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Страница 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Страница 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Страница 143: ...AB Parts...