Publication 1756-UM050A-EN-P - December 2001
Configuring the 1756-ENBT Module
4-7
You can then open the file containing the Relation List at a later
session.
Using RSLinx Software
You can use RSLinx software, version 2.2 or higher, to configure the
1756-ENBT module via a ControlNet or Data Highway Plus network,
or via the serial port on a Logix 5550 processor, if you insert the
1756-ENBT module into a ControlLogix chassis containing:
•
a 1756-CNB module connected to your workstation via
ControlNet, or
•
a 1756-DHRIO module connected to your workstation via DH+,
or
•
a Logix 5550 processor connected to your workstation via its
serial port.
You must have an appropriate communication driver configured in
RSLinx. After configuring the 1756-ENBT module, you can move it to
the chassis where you want to use it.
To configure the 1756-ENBT module using RSLinx, perform the
following steps:
1.
Insert the 1756-ENBT module in the ControlLogix chassis with the
communications module you will be using.
2.
Start RSLinx.
Содержание ControlLogix 1756-ENBT
Страница 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Страница 4: ......
Страница 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Страница 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Страница 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Страница 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Страница 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Страница 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Страница 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Страница 143: ...AB Parts...