62
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
Chapter 5
Connect the 8720MC-RPS Unit
Table 20 - 8720MC Line Reactors for 8720MC-RPS065 Units
Table 21 - 8720MC Line Reactors for 8720MC-RPS190 Units
Table 22 - Wire Ratings for 8720MC Line Reactors
The operating ambient temperature for the 8720MC line reactors is 50 °C
(122 °F), maximum. Derate current 1% for every 1 °C above 50 °C.
Install the Varistor (8720MC-RPS065 units only)
Install a varistor to absorb surge voltage between AC input power wires. The
8720MC-VA-B varistor is the designated varistor for 8720MC-RPS065BM
and 8720MC-RPS065BS units.
Line Reactors
(1)
Cat. No.
(1) Provide the required quantity of reactors for all units connected in parallel (refer to
Continuous Current, max
A
Inductance
uH
Capacity of Motor, max
kW
8720MC-LR03-032B
32
850
15
8720MC-LR05-048B
48
800
22
8720MC-LR10-062B
62
1100
30
8720MC-LR14-070B
70
1200
37
Line Reactors
(1)
Cat. No.
(1) Cooling fan and thermo switch are mounted on the line reactor unit. The thermo switch opens at about 150 °C (302 °F) and
produces a reactor-fan fault signal.
Quantity
Continuous Current, max
A
Inductance
uH
Capacity of Motor, max
kW
8720MC-LR10-100B
1
100
800
65
2
190
125
Line Reactors
Cat. No.
Continuous Current, max
Wire Temperature
8720MC-LR03-032B
≤60 A
105 °C (221 °F) or higher
8720MC-LR05-048B
8720MC-LR10-062B
8720MC-LR14-070B
8720MC-LR14-070B
60…80 A
130 °C (266 °F) or higher
8720MC-LR10-100B
–
105 °C (221 °F) or higher
IMPORTANT
Provide the required quantity of varistors for all units connected in parallel
and connect the varistor on the incoming AC line-side of the AC contactor.