110
Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
Appendix A
Specifications
Technical Specifications
The following table contains technical specifications for the 8720MC-RPS
units.
Attributes
8720MC-RPS065
8720MC-RPS190
Number of Units
Connected in Parallel
(1)
Single Unit
Two Units in Parallel
Three Units in Parallel
Single Unit
Two Units in Parallel
Three Units in Parallel
Capacity of Motor to
be Applied (kW)
37
75
110
125
250
375
Input
Rated capacity of the power
supply (kVA)
45
90
135
152
304
457
Input power factor
(2)
0.95 or higher
Power supply
(3)
324 to 506V AC +10/-15%, 50/60 Hz +/-5%
Rated current, nom (A
rms
)
65
130
195
190
380
570
Current, max 1.0 min (A
rms
)
98
196
294
285
570
855
PWM carrier frequency (kHz)
5, 10 (standard), and 15
5, 10 (standard), and 15
Ou
tp
u
t
Rated output capacity (kVA)
45
90
135
133
266
399
Voltage
750V (standard)
Continuous output current (A
DC
)
64
128
192
190
380
570
Current, max 1.0 min (A)
96
192
288
285
570
855
Bus capacitor (μF)
1960
1960 x 2
1960 x 3
5600
5600 x 2
5600 x 3
Protection functions
Overcurrent, overload, overvoltage, low voltage, and phase loss.
Output signals
RDY signal, FR signal, instantaneous power loss signal, and main magnetic contactor reference contact.
Monitor display (with four-character
seven-segment status indicator
Input current, input power supply voltage, DC bus voltage, power and load ratio.
Input signals
RUN signal, RESET signal, and answer-back signal of the main magnetic contactor.
Env
iro
nme
n
ta
l
Place of installation
In a control cabinet (kept away from corrosive and dangerous gas).
Ambient
Operating
-10…50 °C (14…122 °F)
Storage
-40…65 °C (-40…149 °F)
Heat dissipation (kW)
1.1
1.1 x 2
1.1 x 3
4.0
4.0 x 2
4.0 x 3
Relative humidity
5 to 95% (non-condensing)
Elevation
• Up to 1,000 m (3,300 ft) without derating output power
• For every 300 m (1,000 ft) above 1,000 m (3,300 ft), derate the output power 4%
• Above 1,500 m (5,000 ft), contact Rockwell Automation
Vibration
Less than 1G (25 Hz)
Shock
Less than 2G
Weight kg (lb)
13.5 (29.7)
13.5 (29.7) x 2
13.5 (29.7) x 3
39 (86.8)
39 (86.8) x 2
39 (86.8) x 3
(1) For units connected in parallel, derating is required proportionally to the fluctuation (dispersion) of inductances of AC line reactors connected to phases.
(2) At the rated current of the 8720MC-RPS units.
(3) Applies to 400V rms AC (or 200V rms AC). If you use the unit continuously at a voltage lower than stated, derating is required.