Chapter 6
Communicate over Networks
Devices Included in the Node Count
Any devices that you add directly to the local Ethernet I/O configuration are
counted toward the node limitation of the controller. The following are example
devices that are added to the I/O configuration section in your project and must
be counted:
•
Remote communication adapters
•
I/O modules that are directly connected to the EtherNet/IP network, for
example the 1732E-IB16M12R ArmorBlock®? EtherNet/IP module
•
Motion devices, such as drives
•
Remote controllers
•
HMI devices that are included in the I/O configuration section, for
example, PanelView™ Plus terminals
•
Linking devices, such as the 1788-EN2DNR, Ethernet-to-DeviceNet
linking device
•
Third-party devices that are directly connected to the EtherNet/IP
network
IMPORTANT
While CompactLogix 5370 controllers offer the option of using Ethernet node
count to effectively design a control system, the controllers do have connection
limits on an EtherNet/IP network.
For more information on how to design EtherNet/IP network use in your
CompactLogix 5370 control system, see these resources:
•
The EtherNet/IP Capacity Tool available at
.
The EtherNet/IP Capacity Tool helps you in the initial layout of your
EtherNet/IP network.
•
Ethernet Design Considerations Reference Manual, publication