Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Figure 24 - DC Voltage Signal to Channel 2 Wiring
Connect an IEPE Accelerometer and Non-contact Sensor
shows the wiring of an IEPE accelerometer to channel 1 and the
wiring of a non-contact sensor to channel 2.
Cabl e s hiel d not
conn ecte d at thi s end
Shield
1
17
Channel 2 Input Signal
Signal Common
38
Process DC
Source
TYPICAL WIRING FOR PROCESS DC VOLTAGE SIGNAL
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 2
ATTENTION:
You may ground the cable shield at either end of the
cable. Do not ground the shield at both ends. Recommended practice
is to ground the cable shield at the terminal base and not at the
transducer. Any convenient chassis terminal may be used.
See
Terminal Block Assignments on page 28
IMPORTANT
Verify the Transducer Power Type parameter for channel 1 is set to IEPE so
power is provided to the accelerometer.
See Transducer Object (Class ID 328H) on page 158
. (This setting also sets
the buffered output to the 0…+24 Volt range.)
IMPORTANT
The internal transducer power supply is providing power to the non-
contact sensor. Set the Transducer Power Type for channel 2…-24 V so
that the buffered output ranges from -24…0 Volts.
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......