Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
137
CIP Objects
Appendix B
8
Get/Set
AlarmHAlertLimit
REAL
The threshold value for the alert
state of the alarm. (For range
conditions, this is the greater
threshold value.)
9
Get/Set
AlarmHDangerLimit
REAL
The threshold value for the Danger
state of the alarm. (For range
conditions, this is the greater
threshold value).
10
Get/Set
AlarmLAlertLimit
REAL
The lesser threshold value for the
Alert state of the alarm with a range
condition type.
11
Get/Set
AlarmLDangerLimit
REAL
The lesser threshold value for the
Danger state of the alarm with a
range condition type.
12
Get/Set
AlarmDeadband
REAL
The amount on the safe side of a
threshold by which the value must
recover to clear the alarm.
13
Get/Set
AlarmLimitMultiply (Setpoint
Multiplier)
REAL
Indicates how the threshold must be
adjusted when the Setpoint
multiplication function is invoked.
0 = Disable alarm
> 0 = Multiply the thresholds by the value
14
Get/Set
AlarmLimitMultiplyPeriod
UINT
The amount of time that the
Threshold (Setpoint) Multiplier is
applied after the start-up signal is
received.
Seconds
15
Get/Set
AlarmSpeedRangeEn
BOOL
Indicates whether this alarm is
enabled only within a certain
machine speed range.
0 = No speed range (alarm is always
enabled)
1 = Speed range (alarm only enabled within
speed range)
16
Get/Set
AlarmSpeedHLimit
REAL
Indicates the greater threshold of
the machine speed range for which
the alarm is enabled (disabled at
greater speeds).
CPM
(must be greater than
AlarmSpeedLLimit
)
17
Get/Set
AlarmSpeedLLimit
REAL
Indicates the lesser threshold of the
machine speed range for which the
alarm is enabled (disabled at lesser
speeds).
CPM
(Must be less than
AlarmSpeedHLimit
)
18
Get/Set
Name
STRING2
A name to help identify this alarm.
19
Get/Set
Measurement Identifier
EPATH
Identifies the measurement object
to which this alarm is applied.
See Parameter Object instances 10…25. See
21
Get/Set
Detection Delay
UINT
The period that the measurement
must violate the threshold before
the Alert or Danger status is
indicated.
0…65,530 ms
Table 62 - Alarm Object Instance Attributes (Continued)
Attribute
ID
Access Rule
Name
Data Type
Description
Semantics
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......