
100
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 2
Configure the XM-124 Standard Dynamic Measurement Module
Alarm and Relay Status Parameters
Table 21 - Alarm and Relay Status Parameters
Parameter Name
Description
Values/Comments
Alarm Status
States the current status of the alarm.
Possible status values:
• Normal - The alarm is enabled, the device is in
Run mode, there is no transducer fault, and the
current measurement is not within the Alert or
Danger Threshold value.
• Alert - The alarm is enabled, the device is in
Run mode, there is no transducer fault, and the
current measurement is in excess of the Alert
Threshold value but not in excess of the Danger
Threshold value.
• Danger - The alarm is enabled, the device is in
Run mode, there is no transducer fault, and the
current measurement is in excess of the Danger
Threshold value.
• Disarm-The alarm is disabled or the device is in
Program mode.
• Transducer Fault - The alarm is enabled, the
device is in Run mode, and a transducer fault is
detected on the associated transducer.
• Tachometer Fault - The alarm is enabled, the
device is in Run mode, a tachometer fault
exists, but there is no transducer fault.
• Module Fault - Hardware or firmware failure, or
an error has been detected and is preventing
proper operation of the device.
Relay Status
States the current status of the relay.
Possible status values:
• Activated
• Not Activated
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......