124
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Appendix B
CIP Objects
The dynamic Assembly can include all measurement values that are included in
Assembly Instance 101. In addition, the dynamic Assembly can include these
configuration parameters.
The dynamic Assembly Instance must be instantiated with a call to the class
level Create service. Then the structure can be defined with the
Set_Attribute_Single service for the Member List attribute. Only one dynamic
Attribute instance is supported so subsequent calls to the Create service returns
a Resource Unavailable (0x02) error. The Delete service can be used to destroy
the dynamic Assembly Instance so that it can be re-created.
Table 43 - Instance 199 Component Mapping
EPATH (Where ii = Instance Number)
Class Name
Class Number
Instance
Number
Attribute Name
Attribute
Number
Data Type
21 1D 03 24 ii 30 04
Alarm
31D
h
1…16
Alarm Enable
4
BOOL
21 1D 03 24 ii 30 05
Alarm
31D
h
1…16
Type
5
USINT
21 1D 03 24 ii 30 07
Alarm
31D
h
1…16
Condition
7
USINT
21 1D 03 24 ii 30 08
Alarm
31D
h
1…16
Alert Threshold (High)
8
REAL
21 1D 03 24 ii 30 09
Alarm
31D
h
1…16
Danger Threshold (High)
9
REAL
21 1D 03 24 ii 30 0A
Alarm
31D
h
1…16
Alert Threshold Low
10
REAL
21 1D 03 24 ii 30 0B
Alarm
31D
h
1…16
Danger Threshold Low
11
REAL
21 1D 03 24 ii 30 0C
Alarm
31D
h
1…16
Hysteresis
12
REAL
21 1D 03 24 ii 30 0D
Alarm
31D
h
1…16
Threshold (setpoint) Multiplier
13
REAL
21 1D 03 24 ii 30 0E
Alarm
31D
h
1…16
Start-up Period
14
UINT
21 1D 03 24 ii 30 0F
Alarm
31D
h
1…16
Speed Range Enable
15
BOOL
21 1D 03 24 ii 30 10
Alarm
31D
h
1…16
Speed Range High
16
REAL
21 1D 03 24 ii 30 11
Alarm
31D
h
1…16
Speed Range Low
17
REAL
21 0F 00 24 ii 30 01
Param
0F
h
10…25
Parameter Value (Measurement
Identifier)
1
USINT
21 1D 03 24 ii 30 15
Alarm
31D
h
1…16
Detection Delay
21
UINT
21 23 03 24 ii 30 04
Relay
323
h
1…5
Relay Enable
4
BOOL
21 23 03 24 ii 30 05
Relay
323
h
1…5
Latch Enable
5
BOOL
21 23 03 24 ii 30 06
Relay
323
h
1…5
Failsafe
Enable
6
BOOL
21 23 03 24 ii 30 07
Relay
323
h
1…5
Delay
7
UINT
21 23 03 24 ii 30 09
Relay
323
h
1…5
Alarm Level
9
BYTE
21 0F 00 24 ii 30 01
Param
0F
h
26…30
Parameter Value (Alarm
Identifier A)
1
USINT
21 0F 00 24 ii 30 01
Param
0F
h
31…35
Parameter Value (Alarm
Identifier B)
1
USINT
21 23 03 24 ii 30 0C
Relay
323
h
1…5
Logic
12
USINT
21 23 03 24 ii 30 0E
Relay
323
h
1…5
Relay Installed
14
BOOL
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......