
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
39
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Connect a Passive Transducer
Figures
and
show the wiring of a passive transducer, such as a velocity
sensor, to the terminal base unit.
Figure 19 - Velocity Sensor to Channel 1 Wiring
ATTENTION:
You may ground the cable shield at either end of the
cable. Do not ground the shield at both ends. Recommended practice
is to ground the cable shield at the terminal base and not at the
transducer. Any convenient chassis terminal may be used.
See
Terminal Block Assignments on page 28
IMPORTANT
The module does not power the sensor. It measures only the input
voltage.
Pin A - Common
Pin B - Si gn al
Cabl e s hiel d not
conn ecte d at thi s end
Shield
0
16
Channel 1 Input Signal
Signal Common
37
TYPICAL WIRING FOR COIL-BASED VELOCITY SENSOR
TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE CHANNEL 1
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......