Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
Figure 25 - IEPE Accelerometer and Non-contact Sensor Wiring
Connect Two Accelerometers and a Non-Contact Sensor
shows the wiring of two IEPE accelerometers and a non-contact
sensor to the terminal base. The IEPE accelerometers are wired to channel 1
and channel 2. The non-contact sensor is wired to the tachometer input signal.
Shield
Pin A - S ign al
Pin B - Common
Cabl e s hiel d not
conn ecte d at thi s end
0
16
21
Channel 1 Input Signal
Signal Common
37
SIG
-24
COM
17
1
Signal Common
Channel 2 Input Signal
-24V DC
13
Shield
S h iel d F loat in g
I solat ed Senso r Dr iv er
TYPICAL WIRING FOR IFPF ACCELEROMETER AND NON-CONTACT
SENSOR TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE
WARNING:
Explosion Hazard. You may ground the cable shield at
either end of the cable. Do not ground the shield at both ends.
Recommended practice is to ground the cable shield at the terminal
base and not at the transducer. Any convenient chassis terminal may
be used.
See
Terminal Block Assignments on page 28
IMPORTANT
Verify the Transducer Power Type parameter is set to IEPE for both
channel 1 and channel 2 so power is provided to the accelerometers.
See Transducer Object (Class ID 328H) on page 158
. (This setting also sets
the buffered output to the 0 Volt to 24 Volt range.)
Содержание 1440-SDM02-01RA
Страница 8: ...8 Rockwell Automation Publication 1440 UM001D EN P September 2016 Table of Contents Notes...
Страница 10: ...10 Rockwell Automation Publication 1440 UM001D EN P September 2016 Summary of Changes Notes...
Страница 12: ...12 Rockwell Automation Publication 1440 UM001D EN P September 2016 Preface Notes...
Страница 118: ...118 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix A Status Indicators Notes...
Страница 162: ...160 Rockwell Automation Publication 1440 UM001D EN P September 2016 Appendix B CIP Objects Notes...
Страница 167: ......