Operation 

New heaters 

New heaters need a cleaning period before they are ready for operation. Turn the ventilation to maximum 
position or place the heaters outside in the open air. Fire the heaters for at least two hours on full capacity 
to burn-off oily and greasy remnants of the production. Make sure that after two hours all smoke and 
smell is disappeared. The smoke and smell can be unhealthy, so keep animals and human beings away 
till the heaters and the environment air is clean. 

 
Ignition of the heater  

Always ignite a heater on maximum heat input setting. After a pre heating time of 60 seconds the heater 
can be adjusted to the desired heat input setting. 
Warning: after a heater is extinguished (intentionally or unintentionally) wait always for 3 minutes before 
(re)ignition. This is a worldwide safety rule and intended to ventilate unburned gases away and to leave 
enough time for the thermocouple device to close. 
 

AP-(1,2,3)-F, -FT versions: 

1)  Open  all  gas  taps  (and  turn  the  thermostat  or  gas  pressure 
regulator on maximum). 
2) Keep a flame of a BBQ lighter (or long match) in the ignition hole 
of the burner tube.  
3)  Press  the  knob  of  the  gas  safety  device  and  wait  for  10-25 
seconds after ignition before releasing the knob. 
4) The burner will stay on now.  
5) Repeat al steps again in case the burner directly extinguishes. 

 
Heat regulation of the heater 
AP-(1,2,3)-F version: 

The heat input of this heater can only be changed by adjusting the pressure of the gas supply. Check 
the  gas  supply  pressure  information  on  the  data  plate  of  the  heater  for  the  minimum  and  maximum 
values. If only one pressure is mentioned, adjustment is not possible and only continuous operation or 
on-off operation is allowed. 
 

AP-(1,2,3)-FT version: 

Make sure that the gas supply pressure remains constant at the value 
indicated  on  the  data  plate.  Adjust  the  heat  input  by  setting  the 
thermostat knob at the desired value. Note that the temperature on the 
ground will be several degrees higher than at the sensor. So, use the 
setting on the thermostat knob as a rough guideline and always check 
the real temperature on the ground 

 
Extinguishing the heater 
AP-(1,2,3)-F, -FT versions: 

Close the gas tap or the central gas supply. The burner will extinguish now. The thermocouple safety 
valve will close after 60 seconds.  

 
Visual examination of the flame 

Check after every ignition (and also during regular barn inspection) if a heater still burns correctly. The 
flame  shall  remain  always  inside  the  burner  tube. The  burner  tube  shall  be  equal  red/orange  in  high 
firing position and having a blue flame. 
 
A  burner  does  not  operate  well  in  case  there  is  a  (green)-blue  cloud  inside  the  reflector  and/or  a 
(green)blue flame tongue is coming out the exhaust hole in the reflector. Soot deposit on the reflector 
and  yellow  flames  are  also  a  sign  of  bad  functioning  and  are  not  allowed.  Cleaning  will  solve  these 
problems in most cases. Note that yellow tipping in low fire is allowed. 
 
In high fire position, the flame makes a soft roaring noise. In case the burner makes a loud roaring noise 
and the burner tube does not become equal red/orange, the venturi gauze is damaged and the flame is 
burning inside the venturi tube (back firing). The venturi tube becomes very hot now at the beginning of 
the venturi. Directly extinguish the burner and replace the damaged venturi tube and gauze by a new 
one. 

 

 

 

Approx. Temperature (T) 

Δ  =   15 °C 
*   =   20 °C 

1   =   22 °C 
2   =   28 °C 
3   =   33 °C 
4   =   36 °C 
5   =   38 °C 

Содержание AP-1 Series

Страница 1: ...infra red heaters for use in well ventilated areas Country of destination GB IE MT General international manual AP 1 AP 3 AP 2 AP 1 F AP 3 F AP 3 FT AP 2 F AP 2 FT Alke BV Industrielaan 11a 3925 BD S...

Страница 2: ...t so that nobody accidentally operates the heater Store the heater in a safe place mark that it cannot be used and contact a service agent or gas installer to solve the problem This heater has an open...

Страница 3: ...nature of gas and pressure and adjustment of the appliance are compatible Make sure that the gas and gas line are clean Install a gas filter and condensate trap before the heaters in case the gas or...

Страница 4: ...for more details Beside other important requirements this standard states in short that a 1 5 times room air replacement per hour is sufficient in most situations Also a maximum of 5W heat input per...

Страница 5: ...the gas supply to the burners to extinguish the flames In addition it makes it possible to remove the heaters after use or to service the heaters safely The gas inlet at the heater side is standard a...

Страница 6: ...and away from other people Check if there are no other operating heaters other gas heaters burning candles or people smoking cigarettes in the area Be sure that the valve on the gas cylinder is close...

Страница 7: ...ly one pressure is mentioned adjustment is not possible and only continuous operation or on off operation is allowed AP 1 2 3 FT version Make sure that the gas supply pressure remains constant at the...

Страница 8: ...r gas tightness with leak detection liquid or soapy water according the procedure in the standards applicable in the local installation situation Never use a flame for soundness checks In case a gas h...

Страница 9: ...he gas safety device are the most important parts that maybe requires replacement during normal operational life See the Parts List for more information Replacement thermocouple and magnet unit positi...

Страница 10: ...ing Wrong gas or pressure is used Check data plate with the gas supply Check if the injector or venturi are blocked or dirty Check the injector and venturi size with the table Check if pipe sizes or g...

Страница 11: ...2510000 Burner AP 3 50x80 mm 7 07009000 Distance ring 26 03856000 Suspension frame 155mm AP 2 8 01301000 Injector holder 27 013070xx Venturi 25x62 consult factory 9 01161xxx Injector M8x0 75 consult f...

Страница 12: ...x x I3P G31 1400 20 5 6 0 65 T 1 2 400 g h 0 47 0 22 10 5 1 0063CS3936 I3P G31 1400 20 4 6 0 55 329 g h 0 45 x 11 4 x Ha 1400m I3P G31 2000 20 5 4 0 5 T 1 4 386 g h 0 41 0 22 10 4 x x AP 3 series I2L...

Отзывы: