The gas hose shall be hanging free and have a distance of minimal 1 meter from the ground (AP-1, AP-
3 as much as possible). This to make sure that animals will not damage the hose. Connect the hose via 
an individual gas tap to the central gas supply. 
 
A guideline for placement of the sensor of the temperature regulation is 60 cm above the ground and 
minimal 40 cm away from a heater. Use sensors with a black surface in case the regulation is based on 
measuring the infra-red temperature. 

 

 

 
Gas line supply 

In case a main gas line supplies the gas to the heaters, make sure that an authorised company in your 
country, in accordance with the local rules and requirements, install the system. To avoid problems, use 
galvanised or copper tubing for the gas line. First make a calculation to determine the capacity of the 
whole system and the diameters of the piping in each section. Use the common available calculation 
methods as written in most gas installation standards. Contact an installer or the distributor in case this 
calculation method is not available in your area. For data needed to calculate the dimensions of the gas 
line, see the technical table on the last page. 
 
 The most common way to install a gas line is 
in  the  centre  of  the  barn  (at  least  2  meter 
high) with every 3 to 5 meter a “T” or “cross” 
connection  for  gas  supply  to  the  heaters. 
Always mount a (easy reachable) gas tap at 
the beginning of the gas hose to the heaters. 
This  gas  tap  is  needed  to  close  the  gas 
supply  to  the  burners  to  extinguish  the 
flames.  In  addition,  it  makes  it  possible  to 
remove the heaters after use or to service the 
heaters  safely.  The  gas  inlet  at  the  heater 
side is standard a 8 mm hose nipple (optional a smooth hose  nipple 

or a G1/8” right handed thread. 

Other connections are possible after consultation). Always use approved gas sealant to close the gas 
connections.  

 
Gas cylinder supply 

The gas can also be supplied from LPG gas cylinders. The minimum size is a 11 kg cylinder or larger. 
Before buying a cylinder make sure that the connections of the gas regulator and the gas valve of the 
cylinder are of the same type. Check with your gas supplier for the correct size of gas regulator. Check 
the technical table for the maximum gas consumption and gas pressure.  
 
Store the gas cylinders always on ground level in a well-ventilated place, preferably outside the room 
where the heater is. In case the gas cylinder is placed in a cylinder housing, or cover, make sure that 
there is enough ventilation as requested by the applicable regulations or standards. Never obstruct these 
ventilation  holes. Make sure that the gas cylinders are used  in  upright  position  only and are secured 
again  tipping  over  during  use.  Gas  cylinders  laying  on  their  side  will  give  liquid  gas.  This  is  very 
dangerous and will give a fire ball when it reaches the heaters.  
 
In case the gas cylinder is placed in the same room as the heater is, keep it at a safe distance from the 
heater so it will not be over heated. Advisable is at least 2 meters. Make sure that the gas cylinder valve 
can easily be reached to close the gas supply in  an emergency. Pay special attention how to change 
the gas cylinders in a safe way. 
 

 

Содержание AP-1 Series

Страница 1: ...infra red heaters for use in well ventilated areas Country of destination GB IE MT General international manual AP 1 AP 3 AP 2 AP 1 F AP 3 F AP 3 FT AP 2 F AP 2 FT Alke BV Industrielaan 11a 3925 BD S...

Страница 2: ...t so that nobody accidentally operates the heater Store the heater in a safe place mark that it cannot be used and contact a service agent or gas installer to solve the problem This heater has an open...

Страница 3: ...nature of gas and pressure and adjustment of the appliance are compatible Make sure that the gas and gas line are clean Install a gas filter and condensate trap before the heaters in case the gas or...

Страница 4: ...for more details Beside other important requirements this standard states in short that a 1 5 times room air replacement per hour is sufficient in most situations Also a maximum of 5W heat input per...

Страница 5: ...the gas supply to the burners to extinguish the flames In addition it makes it possible to remove the heaters after use or to service the heaters safely The gas inlet at the heater side is standard a...

Страница 6: ...and away from other people Check if there are no other operating heaters other gas heaters burning candles or people smoking cigarettes in the area Be sure that the valve on the gas cylinder is close...

Страница 7: ...ly one pressure is mentioned adjustment is not possible and only continuous operation or on off operation is allowed AP 1 2 3 FT version Make sure that the gas supply pressure remains constant at the...

Страница 8: ...r gas tightness with leak detection liquid or soapy water according the procedure in the standards applicable in the local installation situation Never use a flame for soundness checks In case a gas h...

Страница 9: ...he gas safety device are the most important parts that maybe requires replacement during normal operational life See the Parts List for more information Replacement thermocouple and magnet unit positi...

Страница 10: ...ing Wrong gas or pressure is used Check data plate with the gas supply Check if the injector or venturi are blocked or dirty Check the injector and venturi size with the table Check if pipe sizes or g...

Страница 11: ...2510000 Burner AP 3 50x80 mm 7 07009000 Distance ring 26 03856000 Suspension frame 155mm AP 2 8 01301000 Injector holder 27 013070xx Venturi 25x62 consult factory 9 01161xxx Injector M8x0 75 consult f...

Страница 12: ...x x I3P G31 1400 20 5 6 0 65 T 1 2 400 g h 0 47 0 22 10 5 1 0063CS3936 I3P G31 1400 20 4 6 0 55 329 g h 0 45 x 11 4 x Ha 1400m I3P G31 2000 20 5 4 0 5 T 1 4 386 g h 0 41 0 22 10 4 x x AP 3 series I2L...

Отзывы: