6-33
ASDI
Operations and Maintenance – TX Models – P/N: 54629
TREE # 2C
Liqui-SAFE VALVE DOES NOT TRIP
RED
IS THERMOCOUPLE
MOLEX PLUG OR
TRANSITION
HARNESS LOOSE
OR
DISCONNECTED?
IS LED LIGHT RED
ON CONTROL
BOARD?
PRESS RED RESET BUTTON TO
RESTART VAPORIZER.
IF PROBLEM REOCCURS THEN:
1. CHECK THERMAL GREASE
COATS LAST 2 INCHES OF
THERMOCOUPLE TIP WHEN
REMOVED FROM
THERMOWELL
2. CHECK THERMOCOUPLE IS
FULLY INSERTED IN THE
THERMOWELL. WHEN FULLY
INSERTED THERMOCOUPLE
SHOULD BOTTOM OUT IN THE
THERMOWELL AND
THERMOCOUPLE SHEATHING
SHOULD COMPRESS TO
SECURE BAYONETT FITTING
3. REMOVE DRAIN PLUG AND
CHECK FOR HEAVY ENDS
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN
CONTACT ASDI OR GO TO “NO”
STEP IF FLOAT OR PRESSURE
SWTITCH ARE INSTALLED.
YES
NO
YES
RECONNECT LOOSE OR
DISCONNECTED MOLEX
OR
REINSTALL WIRES INTO
TRANSITION HARNESS
PRESS RED RESET BUTTON TO
RESTART VAPORIZER
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN GO TO
THE “NO” STEP
IS FLOAT
SWITCH OR
PRESSURE
SWITCH
OPEN?
1. ASSESS SYSTEM
CAPACITY
2. PERFORM SOLENOID
VALVE LEAK TEST.
3. CHECK WIRING.
4. CHECK FUSE LINKS.
IF THE ABOVE ACTIONS
DO NOT FIX THE
PROBLEM CONTACT
ASDI.
REPLACE TEMP.
CONTROLLER.
RESTART
VAPORIZER
NO
YES
OPTIONAL
NO
Содержание TORREXX TX240
Страница 9: ...ASDI Operations and Maintenance TX Models P N 54629 1 2 Figure 1 TORREXX SSR Dimensional Drawing ...
Страница 52: ...APPENDIX A TECHNICAL INFORMATION ...
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 80: ...ASCO Valve used by Algas SDI ...
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......