4-21
ASDI
Operations and Maintenance – TX Models – P/N: 54629
1) Close the outlet isolation valve.
2) Open all valves between the storage tank and the vaporizer to allow liquid
flow to the vaporizer when the solenoid valve opens.
3) Apply power. If the upper control box lid is off, the solid-state relay LED lights
should come on. The vaporizer heating elements are now energized. It will
take approximately 60 seconds for the vaporizer to reach operating
temperature. After reaching the operating temperature, the inlet solenoid
valve will open automatically to allow LPG to enter. Wait approximately 2
minutes for excess LPG to be pushed back to the storage tank.
4) Carefully press the Button on top of the Liqui-SAFE
TM
valve all the way down
and SLOWLY release it. A latch mechanism inside the Liqui-SAFE
TM
valve
will keep the red flag in the down position, indicating the valve is open and in
operating position.
5) The TORREXX
TM
is now ready to supply vapor. Slowly open the outlet
isolation valve to pressurize the supply piping. Then, fully open the outlet
isolation valve to allow vapor to flow to the load. Heater will cycle
automatically to match the flow conditions.
NOTE
Do not fill tank above 90% full. When the tank is overfilled, the
vaporizer cannot push liquid back to the tank.
STOPPING THE VAPORIZER
1) Close the outlet isolation valve.
2) Disconnect power.
PURGING THE VAPORIZER
Purging procedure should be followed anytime a vaporizer needs to be
maintained, serviced, relocated, or shut down for any other reason.
CAUTION
Prior to purging the vaporizer, ensure there are no closed ball
valves or back check valves restricting the flow of liquid to the tank.
1) Close the valve at the outlet of the vaporizer.
2) If the vaporizer is not operating, start the vaporizer.
3) Allow 5 minutes for vaporizer to heat up and push most of the remaining
liquid back into the tank.
4) Close the tank liquid outlet valve.
5) Open the vaporizer outlet valve and flare or allow attached equipment to
consume remaining gas in the line.
Содержание TORREXX TX240
Страница 9: ...ASDI Operations and Maintenance TX Models P N 54629 1 2 Figure 1 TORREXX SSR Dimensional Drawing ...
Страница 52: ...APPENDIX A TECHNICAL INFORMATION ...
Страница 59: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 63: ......
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......
Страница 80: ...ASCO Valve used by Algas SDI ...
Страница 82: ......
Страница 83: ......
Страница 84: ......
Страница 85: ......