6-31
ASDI
Operations and Maintenance – TX Models – P/N: 54629
CHECK CONTROL BOARD LIGHT
TREE # 2A
Liqui-SAFE VALVE DOES NOT TRIP
GREEN
NO LIGHT
CHECK
TRANSFORMER
WIRING
LOOSE
WIRING?
YES
BAD WIRING
CONNECTIONS.
REPLACE OR REPAIR
ANY DAMAGED WIRING
NO
CHECK
TRANSFORMER FUSE
BLOWN
FUSE?
YES
REPLACE FUSE AND
RESTART
VAPORIZER
NO
REPLACE TRANSFORMER
AND RESTART VAPORIZER.
PROBLEM
FIXED?
NO
IS THE PROBLEM
FIXED?
NO
REPLACE
TEMPERATURE
CONTROLLER.
RESTART VAPORIZER
PROBLEM CAUSED BY
A BLOWN FUSE.
YES
SEE TROUBLESHOOTING
TREE #2B
CHECK
INCOMING
POWER
INCOMING
POWER OK?
YES
NO
CORRECT
INCOMING
POWER ISSUE
YES
SEE TROUBLESHOOTING
TREE #2C
RED