Troubleshooting
5-30
Algas-SDI Operation and Maintenance Manual
– P/N - 52642
TROUBLESHOOTING TREE #4
MAIN BURNER WILL NOT LIGHT
CHECK TO SEE THAT THE
PILOT IS IMPINGING ON THE
THERMOCOUPLE BULB,
APPROXIMATELY 3/8” TO 1/2”
(9 to 13 mm)
TURN THE THERMOSTATIC GAS VALVE
TEMPERATURE CONTROL DIAL UP TO
THE HIGHEST SETTING. DID THE
CONTROL “CLICK”?
CHECK FOR
PLUGGED GAS
LINE TO THE
BURNER
NO
YES
SEE TROUBLESHOOTING TREE
#1 OR #2 TO CHECK
THERMOCOUPLE AND
REGULATOR
REPLACE
THERMOSTAT
YES
NO
Содержание Direct Fired 120/60H
Страница 4: ...This page left intentionally blank...
Страница 6: ...This page left intentionally blank...
Страница 9: ...This page left intentionally blank...
Страница 42: ...APPENDIX A TECHNICAL INFORMATION...
Страница 43: ...Figure 13 40 40H Vaporizer Replacement Parts 1 2 3 4 5 6 10 8 9 11 12 13 14 15 16 24...
Страница 55: ......