Faulty or poorly 
connected pump  

and then unscrew 
the plastic cap on 
the thermostat 
and press the 
reset button 

 
Contact service 

Faulty thermostat 

 
 
Er02 

 
 
Safety pressure switch activation 

 
Obstruction of flue 
gases 

 
Press and hold P2 
key longer than 3 
seconds 

Check soiling of 
flue pipes and 
chimney 

Incorrect chimney 
installation 

 
Contact service 

Faulty manometer 

 
 
 
Er03 

 
 
Shutting down due to the low flue 
gases temperature 

 
Poor combustion (too 
much or too little of 
pellet remains in the 
combustion chamber) 

 
Allow the boiler to 
shut down and 
then press and 
hold P2 key longer 
than 3 seconds 

Check the size of 
pellet granules 
Check soiling of 
furnace chamber 

Pellet tank empty 

Check condition of 
flue pipes 

Faulty flue gases probe 

Contact service 

 
 
Er05 

 
Shutting down due to the high flue 
gases temperature 

The flue gases 
temperature exceeds 
the limit 

 
Allow the boiler to 
shut down and 
then press and 
hold P2 key longer 
than 3 seconds 

Insufficient heat 
transfer – Contact 
service 

Obstruction of flue gas 
pipes 

Check soiling of 
flue gas pipes and 
chimney 

Faulty flue gas probe 

 
Er07 

 
Encoder error  

 
Encoder signal missing 

Allow the boiler to 
shut down and 
then press and 
hold P2 key longer 
than 3 seconds 

 
Contact service 

 
Er08 

 
Encoder error 

The flue gas motor is 
not reacting 

Allow the boiler to 
shut down and 
then press and 
hold P2 key longer 
than 3 seconds 

 
Contact service 

The flue gas motor is 
working faster or 
slower than set 

 
 
Er11 

 
 
Clock error 

Problems with the 
internal clock 

 
Press and hold P2 
key longer than 3 
seconds 

Check the 
accuracy of set 
time set  

 
Insufficient capacity of 
internal battery 

Check the 
correctness of 
programming in 
Chrono mode 
Contact service 

 
 
 
Er12 

 
 
 
Boiler ignition failure 

Boiler ignition error 

 
Allow the boiler to 
shut down and 
then press and 
hold P2 key longer 
than 3 seconds 

Check the 
condition and 
quality of used 
pellet 

During Ignition Phase 
the adequate flue 
gases temperature has 
not been achieved 

Check soiling and 
draft of flue gas 
pipes and chimney 

Faulty flue gas probe 

Contact service 

Содержание GRANDE 37

Страница 1: ...1 A D METALNA INDUSTRIJA VRANJE Radni ka br 1 PELLET BOILER GRANDE 37 INSTRUCTIONS FOR USE MAINTENANCE AND INSTALLATION ENG V 1 0_JUN 2018...

Страница 2: ...placed above the boiler part of the plant Fuel pellets are filled from above through the lid to be used for that purpose Make sure that the boiler is properly dimensioned with respect to the heating s...

Страница 3: ...G 9 7 2 INSPECTION AND PARTS THAT NEED TO BE MAINTAINED 10 7 3 ADDITIONAL MAINTENANCE 10 8 IMPORTANT SAFETY INFORMATION 10 9 PELLET QUALITY IS VERY IMPORTANT 10 9 1 PELLET STORAGE 11 10 BOILER CONTROL...

Страница 4: ...tandards or notes contained in this User Guide accidents and or damage that occurred due to improper or incorrect use by the user accidents and or damage due to modification or maintenance without aut...

Страница 5: ...the existing devices If the existence of the above indicated is established the installation can begin Follow with due attention the manufacturer s instructions the current safety norms and standards...

Страница 6: ...riers for the regulation of the flow of flue gases The connector of the 80 mm flue pipe from the pellet boiler to the chimney should have the following characteristics total length of up to 5 m in the...

Страница 7: ...oregoing requirements Section 3 1 Figure 3 An uptake should be grounded in accordance with the applicable regulations Grounding is legally defined and regulated Grounding should be independent of the...

Страница 8: ...ed led back to flue gas pipes or should enter the chimney of a greater diameter 110 120 mm Care should be taken not to use bends of a sharp angle of 90 They must be of a certain radius or made in segm...

Страница 9: ...an electrical cable for medium temperature If the power cord is damaged it must be replaced so contact our authorized service Before starting work on the electrical connection care should be taken abo...

Страница 10: ...boiler are 1 Non return valves should also be 1 or larger If the non return valve is not installed the guarantee will not apply Diagram for installation of non return valve 1 Boiler Grande 2 Circular...

Страница 11: ...boiler is a combustion device During operation some parts may heat up to very high temperatures The pellet boiler is a class C1 designed to burn wood pellets pellets with a 6 mm diameter maximum 30 m...

Страница 12: ...or a cleaning procedure follow the following safety rules Turn the pellet boiler off before beginning any procedure Make sure that the boiler is cold before beginning any procedure on the boiler Vacu...

Страница 13: ...procedure professionally you should contact the chimney sweep ADDITIONAL MAINTENANCE Your pellet boiler is a source of heat in which only pellet may be used Annual maintenance of the boiler can only b...

Страница 14: ...on of the boiler due to the use of low quality pellets Pellets should be in accordance with the DIN Standard 51731 DIN plus Norm 7135 or other comparable European standards PELLETS SHOULD NOT BE KEPT...

Страница 15: ...n Block Mode press and hold the key for 3 s and longer after the acoustic sound P4 P6 Change values Change values and settings in menus and submenus Browse menus and sub menus Browse menus and submenu...

Страница 16: ...over Ignition Block Off Errors Alarms If error alarm occurs system switches to Block Mode Error Code Alarm Code Error Alarm Description Er01 Safety Thermostat Activated Er02 Safety Manometer Activated...

Страница 17: ...s if the system is in Standby Mode due to pressed P5 key Visualizations By pressing keys P4 and P6 you enter the Visualization Menu In this menu some values of system parameters can be seen L3 On P1 P...

Страница 18: ...ters Chrono The menu for the Chrono program modalities and ignition extinguishing times Manual Load The menu for the manual auger loading Possible only if the system is in OFF state Time and Date The...

Страница 19: ...step the value is increased or decreased by 5 Example Calibration value 3 3 5 15 This means that the calibration value of the auger speed will be decreased by 15 in relation to default value Default...

Страница 20: ...ty By opening the Chrono Menu two sub menus are visible Modality and Programming By pressing P4 and P6 keys choose one of sub menus and open it by pressing P3 key The Modality Menu contains the follow...

Страница 21: ...for each day Weekly Program programming system start up shut down time for the whole week There are three time intervals available Week End Program select between two periods Monday Friday and Saturda...

Страница 22: ...to start up the boiler Following ignition phases are Check Up Phase During Check Up Phase initial test of correctness on boiler input signal probes and manometers is performed During this phase flue...

Страница 23: ...ditions is achieved 1 When the boiler reaches the set water temperature it switches to modulation and continues to increase temperature of water by inertia to the value of 4 C higher than the set wate...

Страница 24: ...longer than 3 seconds Insufficient heat transfer Contact service Obstruction of flue gas pipes Check soiling of flue gas pipes and chimney Faulty flue gas probe Er07 Encoder error Encoder signal missi...

Страница 25: ...ey longer than 3 seconds Check and clean primary air inflow pipes Check soiling and draft of flue gas pipes and chimney Obstruction of flue gas pipes Inadequately closed door during the ignition phase...

Страница 26: ...power consumption during operation of the boiler W 53 Minimum power consumption during operation of the boiler W 37 Largest electricity consumption when starting the boiler W 310 Electrical consumpti...

Страница 27: ...24 13 DIMENSIONS OF BOILER GRANDE 37 Figure 15...

Страница 28: ...RKS 1 Pellet boiler Grande 37 2 Automatic air vent 3 Safety valve 4 Hydraulic separator 5 Circulator pump 6 Expansion vessel 7 Circulator pump 8 Non return valve 9 Three way valve with pipe thermostat...

Отзывы: