8
Check and note the
A
measure.
9
Loosen and remove the locking bolts. Identify
them according to
on page
55.
NOTE
Brush the threads of the tightening bolts
with a steel wire brush and then grease
the threads before loosening the
tightening bolts.
10
Use the tightening bolts to open the plate
heat exchanger. During the opening
procedure, keep the frame plate and pressure
plate parallel. Skewing of the pressure plate
during opening must not exceed 10 mm (2
turns per bolt) across the width and 25 mm (5
turns per bolt) vertically.
Loosen the four tightening bolts (1), (2), (3),
(4) diagonally until the plate pack measure is
1.05×
A
making sure that the frame plate and
pressure plate are parallel while opening.
Continue alternating between each bolt until
all reaction forces of the plate pack have
disappeared. Then remove the bolts.