Installing the SF/CPM
7750 SR-12
Page 87
To install a SF/CPM:
Step 1
Remove the SF/CPM module from the packaging. Do not touch the printed circuit board
or connector pins.
Step 2
Hold the SF/CPM by the edges and then rotate the ejector levers inward toward the
faceplate.
Step 3
Align the card with the slot guide. Slide inward until the pins engage with the backplane
connectors.
Step 4
Simultaneously, rotate the ejector levers outward to lock the backplane connectors and
SF/CPM in place.
If an SF/CPM ejector lever does not shift to the locked position, the card is probably not
seated properly in the backplane. Pull the card out halfway and then reinsert it. Shift the
levers to the locked position.
Step 5
Secure the card in place by tightening the captive screws.
Step 6
(Optional) Install the redundant SF/CPM in the other center chassis slot.
Step 7
Establish a console connection on the active CPM. See