Site Preparation
7750 SR-12
Page 43
F
ANS
The 7750 SR-12 cooling system must have at least 3-inches of unrestricted unobstructed front
and rear air flow to function properly. 9-inches are recommended.
At least 2 impeller trays (fan trays) must be installed before you supply power to the chassis.
Blank panels and faceplates are required in all empty card and component slots to prevent
excess dust accumulation and to help control airflow and electromagnetic interference.
33
A
IR
F
ILTER
The air filter tray must always be installed while the 7750 SR-12 is powered up. The air filter
is factory installed.
Filters should be inspected monthly and cleaned and replaced every twelve months or as
required. The filter is field replaceable.
S
TORAGE
To store unused components and extra field-replaceable parts, re-wrap the components in the
original packaging and keep them in a dry, dust-free temperature controlled environment.
Table 15: Storage Specifications
Parameter
Description
Storage temperature
From -40° to 158°F (-40° to 70°C)
Non-condensing relative humidity
Within 5 to 95 percent.
Содержание 7750 SR-12
Страница 1: ...7750 SR 12 INSTALLATION GUIDE Document Part Number 93 0019 01 December 2003 ...
Страница 6: ...Page 4 7750 SR 12 Table of Contents ...
Страница 14: ...Page 12 7750 SR 12 ...
Страница 84: ...Monitoring AC Power Page 82 7750 SR 12 ...
Страница 100: ...Establishing Router Connections Page 98 7750 SR 12 ...
Страница 150: ...Impeller Trays Page 148 7750 SR 12 ...
Страница 156: ...Cable Pin Assignments Page 154 7750 SR 12 ...