![Alcatel 7750 SR-12 Скачать руководство пользователя страница 68](http://html1.mh-extra.com/html/alcatel/7750-sr-12/7750-sr-12_installation-manual_2891366068.webp)
Installing DC PEMs
Page 66
7750 SR-12
Notes:
• The remote power source (circuit breaker panel, outlet, etc.) must be easily accessible.
• Each DC-input PEM requires a dedicated 100A (maximum) service.
• Cables are not provided. In the United States, use #6 AWG, high strand count copper wire. If the
7750 router is located outside the USA, consult local and national electrical code for proper wire
sizing.
• For the DC PEM terminal block, lugs are provided. If they are missing or misplaced, use a
Panduit LCC F6-14A copper, standard barrel, 2-hole lug with two 1/4-inch (.635 cm) diameter
holes on a 3/4-inch (1.905 cm) spacing (0.250-20 UNC).
• Two PEM slots are located at the bottom rear of the chassis (see
). The slots are not labelled but for documentation purposes the top slot is referred to as
slot “1” and the bottom slot is referred to as slot “2”. For full redundancy two PEMs must be
installed and each PEM must be attached to an independent power source with a dedicated circuit
breaker. One -48 DC,100A (maximum) branch circuit is required for each PEM.
• The 7750 SR-12 requires a minimum of one DC power entry module (PEM) to operate, but two
are recommended for redundancy. When two PEMs are installed, they share the electrical load
equally as long as both PEMs are operational. If one PEM fails, the remaining PEM provides the
power the router requires for normal operation.
• For full redundancy, each power supply module should be attached to an independent power
source with a dedicated circuit breaker.
Содержание 7750 SR-12
Страница 1: ...7750 SR 12 INSTALLATION GUIDE Document Part Number 93 0019 01 December 2003 ...
Страница 6: ...Page 4 7750 SR 12 Table of Contents ...
Страница 14: ...Page 12 7750 SR 12 ...
Страница 84: ...Monitoring AC Power Page 82 7750 SR 12 ...
Страница 100: ...Establishing Router Connections Page 98 7750 SR 12 ...
Страница 150: ...Impeller Trays Page 148 7750 SR 12 ...
Страница 156: ...Cable Pin Assignments Page 154 7750 SR 12 ...