Fused Load Lead Harness Connection
4200-097
11-1
Revision 1.06
11.
Fused Load Lead Harness Connection
There is a maximum of 20 load connections available. The quantity used is dependent on the battery
configuration. The installation kit will include the appropriate quantity of harnesses for the configuration
ordered. Depending on the configuration, as few as three or as many as twenty load connections will be
required. To identify quantities and connection locations, refer to the Load Inputs section of the
Configuration Connection Diagram at the back of this manual. Each configuration on this drawing shows
exactly where these cables connect to the battery. Sometimes this connection will be made on one of
the tabs of a double tab washer and, at other times, it will be positioned on a single tab. It is critical in
cases where it is used on a single tab that the load connection be placed closest to the battery post.
Before installation, verify that the fuse is not installed. The fuse will be installed at time of startup. As
the cables are routed and inserted into the connector on the rear of the unit, apply a number label that
associates the cable to the proper Load Input connection. Proper location and termination of these
cables is critical and could cause equipment failures if done improperly.
Figure 14 - Fused Load Lead
Figure 15 - Load Input Connections
Note
: It is very important that the load connection is the closest connection to the post if two tab
washers are used. Failure to do this could result in inaccurate resistance readings.
Caution
: Connecting the load wires incorrectly could cause an equipment failure if a resistance
test is performed. Such failures are not covered under warranty.
Warning:
Do not install load lead fuses until instructed to do so in the Getting Started Guide.