Unit Configuration
4200-097
8-3
Revision 1.06
8.3
Power Setting Selection
The power setting indentifies what load input wires will provide power to the equipment. There are
three possible settings described in the chart below. In the chart, the battery configuration is defined as
Number of Strings x Number of Jars/Cells x Voltage of each Jar/Cell.
Battery Configuration
Power Setting
1X18X1V
B
1X12X2V
B
2X12X2V
B
1X24X2V
C
1X6X4V
A
2X6X4V
A
3X6X4V
A
4X6X4V
A
1X12X4V
C
2X12X4V
C
1X4X6V
C
2X4X6V
C
3X4X6V
C
4X4X6V
C
1X8X6V
C
2X8X6V
C
3X8X6V
C
1X3X8V
B
2X3X8V
B
3X3X8V
B
4X3X8V
B
1X6X8V
B
2X6X8V
B
3X6X8V
B
4X6X8V
B
1X2X12V
A
2X2X12V
A
3X2X12V
A
4X2X12V
A
1X4X12V
C
2X4X12V
C
3X4X12V
C
4X4X12V
C