UXIM Specifications
4200-106
20-2
Revision 3
20.2
Cell Measurements
This section describes cell measurement specifications.
Parameter
Tolerance
Cell Voltage
0 to 3V, 0.1%
2mV
Internal Cell Resistance
0 to 32,000µ
, 5% of reading ±2
Intercell Resistance
0 to 5000µ
, 5% of reading ±5
Intertier/charge cable Resistance
0 to 5000µ
, 5% of reading ±5
Cell/Monobloc Temperature
0
C to 80
C ±0.1
C (32
F to 176
F)
Table 6 - Cell Measurement Specifications
20.3
System Measurements
This section describes system measurement specifications.
Parameter
Tolerance
Number Of Inputs
String Voltage
85Vdc to 150 Vdc ± .5%
Calculated
String Current
0 to 2000ADC ±1% of full scale
Calculated
Ripple Current
0 to 250 Amperes RMS,
±5% of full scale
Calculated
Float Current
0 to 5000mADC,
±50mA
Calculated
Ambient Temperature
0
C to 80
C±0.1
C (32
F to 176
F)
1
Table 7 - System Measurement Specifications