ensure that the water filters at the water inlet are cleaned before finally
connection the boiler to the water installation.
Check that no dirt is left in either the gas or water pipe work as this could
cause damage to the appliance.
4.2 FLUE SYSTEM AND INSTALLATION
4.2.1 Sitting the Flue Terminal
The flue must be installed according to national and local regulations
(See Fig. 13).
The terminal must not cause an obstruction or the discharge cause a
nuisance.
If the terminal is fitted within 1000 mm of a plastic or painted gutter or
HARMONY_D USERS INSTALLATION AND SERVICE MANUAL
23
Figure 12 Gas & Water Connections
4.2 FLUE SYSTEM AND INSTALLATION
4.2.1 Sitting the Flue Terminal
The flue must be installed according to national and local regulations (See Fig. 13).
The terminal must not cause an obstruction or the discharge cause a nuisance.
If the terminal is fitted within 1000 mm of a plastic or painted gutter or within 500 mm of
painted eaves, then an aluminum shield at least 1000 mm long should be fitted to the
underside of the gutter or painted surface.
The terminal should be fitted less than 2 meters above a surface to which people have access.
In certain weather conditions a terminal may steam and sitting where this could cause a
nuisance should be avoided.
Take care to ensure that combustion products do not enter ventilated roof voids.
Where elongation of the flue pipe is a necessary, only original extension pipe and elbow must
be used.
The flue system can be installed from inside the room without access to the external wall and
Содержание HARMONY - D
Страница 1: ...1 USERS INSTALLATION AND SERVICING INSTRUCTIONS HARMONY D ...
Страница 2: ...2 Code No A 1 2 8i Publishing Date 200114 Revision Date 200114 ...
Страница 36: ...36 HARMONY_D USERS INSTALLATION AND SERVICE MANUAL 27 Figure 15 Wall Connections Figure 16 Extensions Elbow ...
Страница 70: ...70 HARMONY_D USERS INSTALLATION AND SERVICE MANUAL 55 Appendix A FAULT DETERMINATION ...
Страница 71: ...71 ...