13
Fresh water must be added periodically to the plumbing. The chalk and other
chemicals will connect with the system and become solid. For avoiding this
closed expansion tank must be used in the system. In the systems that closed
expansion tanks are used, water will flow in closed system so it will not evaporate
and lost. So in this kind of systems the water level wiill stay same and fresh
water addition will not be necessary. This will prevent chalk and dust and the life
of the ssytem will be long.
PLUMBING INSTRUCTIONS
•
The water in the radiator or heating system is not healthy. Do not use this
water as drinking or cleaning water. Do not take water from the system. If
the water level is low water addition is needed.
•
For avoiding chalk and other chemical dust problems soft water must be
used in the system. Plumbing system water quality: Ph > 7,2 Th < 25 °Fr.
•
If the city sanitary water is not in requested quality water addition from
wells or other sources must be made after testing it. For reaching the
requested quality additional processes must be applied to the water if
needed.
•
For avoiding the chalk and other dust to get in to the boiler, or from boiler
to plumbing system dust holders must be placed in and out line of the
system.
•
Circulation pump must be connected to the water output of the boiler and
the capacity of the pump must be suitable to the boiler capacity. If not,
problems may occur in flowing of the water and heating efficiency of the
boiler.
•
For working the system properly 4 way mixture valve or thermostatic control
by-pass pump must be used for increasing return water temperature.
•
By connecting a three way motor valve between the forward and return
line of heating system, the water that flows to the system can be controlled
in ratios.
•
There must be water inside of the boiler every time. If not corrosion can
occur in the boiler and the plumbing system. If the boiler will not be used
in winter season, for avoid freezing anti-freeze solution must be used.
Содержание ADK 200
Страница 1: ...Operation Manual ADK 200 HEATING SYSTEM CAST IRON BOILERS WITH LIQUID GAS FUEL...
Страница 2: ...Kitap Revizyon Tarihi 310706 Kitap Bask Tarihi 310706 Kitap Revizyon No 1...
Страница 3: ...ADK 200 HEATING SYSTEM CAST IRON BOILERS WITH LIQUID GAS FUEL Operation Manual...
Страница 4: ......
Страница 6: ......
Страница 12: ...10 ADK 200 CAST IRON BOILER TECNICAL DATA...
Страница 13: ...11 ADK 200 CAST IRON BOILER DIMENSIONS...
Страница 18: ...16 INSTRUCTIONS ABOUT FLUE...
Страница 20: ...18 BOILER CONTROL PANELS...
Страница 21: ...19 ELECTRICAL DIAGRAMS...
Страница 27: ...25 DIAGRAMS GASSIDERESISTANCE EXITFLUEGASRESISTANCE...