After the installation of the boiler
all
the water and fuel
connections and
valves
must
be
controlled for leakage.
x
For ACK2 and ACK3 type
boilers, it is advisable
to have a
three-way valve
between flow and return line in order to keep the water return line over
55 °C in order to overcome condensation problem.
x
ACK2
and ACK3
boilers have condensation outlet which is on the boiler
flue gas side, this outlet shall be drained with a siphon in order to
prevent flue gas leakage from boiler. Condensation drain shall be
according to local codes.
x
ACK2 and ACK3
boilers, it is advisable
to have the circulation pump on the
flow direction at closed expansion systems and on the return line on open
vented expansion systems.
x
For ACK2 and ACK3
boilers, it is advisable
to have the safety valve on flow
line to the connection present on the boiler outlet pipe without any valve.
x
For connection of the closed expansion tank it is advice to have on return
line and a lockable valve + drain valve is advised only for servicing.
x
If necessary, national regulations regarding the condensate waste disposal
rules shall be applied.