7
contamination of the combustion air by high levels of dust or halogenated
hydrocarbons (e.g. Solvents, spray can propellants, cleaning agents,
adhesives, etc.) must be avoided. The humidity level must not be high in
boiler rooms.
x
The boiler room must not be used for other purposes and must not have
an open connection to the other closed living areas. Connection door
must be air tight, fire resistant and self closing.
x
The oil or gas burners are equipped with an ignition device which
automatically lights the pilot, and some more additional automated safety
controls. Do not try to light the burner or operate the system manually.
All the control devices must be functional and operating with in the limits
specified at all the time. If any of them is null functioning do not operate
the system and call a qualified service.
x
If the boiler is heated above 90 °C, do not supply cold water to the system
for rapid cool down. It can cause an explosion. Wait the boiler cool down
naturally up to 40 °C before adding make up water.
x
Do not use this appliance if any part has been under water. Immediately
call a qualified service to inspect.
x
An emergency shut down switch must be placed in a proper place outside
the boiler room. This switch must cut off the fuel line and must be identified
by a name plate.
x
In starting a new installation or if fuel lines have been disconnected after
servicing, air must be purged from the fuel lines by a qualified person.
x
In closed expansion systems with a membrane type expansion tank,
tank gas pressure must be controlled regularly by a qualified service. If
the pre-charge gas pressure is less then specified; then the system
pressure will rise enormously and can cause an explosion.
x
If the system is running with a fuel heavier then air and the boiler room is
under ground level, then the firing system must have a flame control
device and the possible leakage from fuel lines must be ventilated to a
safe place by ex-proof mechanical means.
x
If there is a fuel, flue gas or water leakage in the system, stop the burner
and call the responsible authority.
x
After commissioning the repair, maintenance work is under responsibility
of user and must be done with a qualified person.
x
Before operating, smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier then the air and will
settle on the floor.
Содержание ACK2
Страница 1: ...Operation Manual ACK2 ACK3 HEATING SYSTEM BOILERS WITH LIQUID GAS FUEL...
Страница 2: ...Code No A 4 1 3 i Published on 210910 Revision No 210910...
Страница 4: ......
Страница 33: ...BOILER CONTROL PANEL WIRING DIAGRAMS 33...
Страница 36: ...ANNEXES 36...
Страница 37: ...37...
Страница 38: ...38...
Страница 39: ...39...
Страница 40: ...40...
Страница 41: ...41...