Commissioning Checks
as a general precaution and check before installation, always ensure the supply pipework to the shower
has been fully purged with at least 20 litres (2 buckets) of water through it
before the flow sensor is
installed
. any building debris in the water supply will adversely affect the sensor function and may also
damage the shower heater/mixer.
Install pump according to these instructions. failure to do so may void warranty.
Confirm all push-fit pipes are fully inserted 20mm into fittings.
brush out all dust, grit and debris
from shower tray
Thoroughly clean out waste
Confirm shower water supply pipework is flushed
before connecting to the shower sensor via the filter
Turn on power to Pump
Turn shower on low flow and confirm pump
operates after Start Delay (default 5 secs.)
Run for 2-3 mins
Set shower to Maximum flow
follow the Calibration setting, adjust pump speed on
controller to match maximum shower flow
adjust RUn-on and repeat until tray is cleared and
pump stops with minimum RUn-on
Switch shower off.
Pump will RUn-on
If you experience problems see
Problem Solving section