7.- Operation
7.1.- Compressor control
NORMAL OPERATION
If Pump Down is deactivated (P26=0), the compressor and the solenoid behave in the same way.
If Pump Down is activated (P26=1), the compressor and the solenoid behave as defined in section 7.5.
“CHANGE OF SET POINT” FUNCTION
It modifies the refrigerated facility's set point value.
It can be activated after a certain time has elapsed (defined in parameter
C11
) without activity in the cold room
door, to do this one of the digital inputs such as “door contact” (
P10 or P11 = 1
) must be configured.
Optionally, you can activate and deactivate this mode at will, using an external switch, configuring one of the
digital inputs as “Change set point” (
P10
or
P11
= 4).
If we set the
C11
parameter to 0, it can only be activated by external switch.
ON
SP
SP+Dif.
OFF
COMP.
ºC
When the temperature in probe 1 reaches the set
point value (
SP
) plus the differential of the probe
(
C1
), the compressor and solenoid are activated and
the temperature drops. When the set point value (
SP
)
is reached, the compressor and solenoid stop.
ON
SP+C12 (SP+C12)+C1
OFF
COMP.
ºC
Operation is the same as in the normal ode, but increasing the set point the
amount of degrees defined in the
C12
parameter.
7.- Operation
7.1.- Compressor control
NORMAL OPERATION
If Pump Down is deactivated (P26=0), the compressor and the solenoid behave in the same way.
If Pump Down is activated (P26=1), the compressor and the solenoid behave as defined in section 7.5.
“CHANGE OF SET POINT” FUNCTION
It modifies the refrigerated facility's set point value.
It can be activated after a certain time has elapsed (defined in parameter
C11
) without activity in the cold room
door, to do this one of the digital inputs such as “door contact” (
P10 or P11 = 1
) must be configured.
Optionally, you can activate and deactivate this mode at will, using an external switch, configuring one of the
digital inputs as “Change set point” (
P10
or
P11
= 4).
If we set the
C11
parameter to 0, it can only be activated by external switch.
When the temperature in probe 1 reaches the set
point value (
SP
) plus the differential of the probe
(
C1
), the compressor and solenoid are activated and
the temperature drops. When the set point value (
SP
)
is reached, the compressor and solenoid stop.
9