1763H532 Ed.02
Level 1.- ALARM CONTROL
Level 1.- GENERAL STATUS
Description
Units
Min
Def
Max.
A0
Configuration of temperature alarms (Page 14):
0
=Relative to SP
1
=Absolute
0
1
1
A1
Maximum alarm probe 1 (must be greater than SP) (Page 14)
(ºC/ºF)
A2
99,0
99,0
A2
Minimum alarm probe 1 (must be greater than SP) (Page 14)
(min.)
-45
-45
A1
A3
Temperature alarm delay during start-up (Page 15)
(min.)
0
0
120
A4
Temperature alarm delay after completion of a defrost (Page 15)
(min.)
0
0
99
A5
Temperature alarm delay after reaching the value of A1 or A2 (Page 15)
(min.)
0
30
99
A6
External alarm delay when receiving digital input signal (P10 or P11=2 or 3) (Page 15)
(min.)
0
0
120
A7
Deactivation delay of the external alarm when the signal of the digital input disappears
(P10 or P11=2 or 3) (Page 15)
(min.)
0
0
120
A8
Show warning if defrost is terminated by time-out
0
=No,
1
=Yes (Page 14)
0
0
1
A10
Temperature Alarm Differential (A1 and A2) (Page 14)
(ºC/ºF)
0,1
1,0
20,0
A12
Door open alarm delay (if P10 or P11=1) (Page 14)
(min.)
0
10
120
EP
Exit Level 1
Level 2
Description
Units
Min
Def
Max.
P1
Delay of all functions on receiving electrical power
(min.)
0
0
255
P2
Función del código de acceso (password) (Pág. 15)
0
= Inactivo;
1
= Bloqueo acceso a parámetros;
2
= Bloqueo del teclado
0
0
2
P3
Configures the default factory settings
0
= No changes
1
=Return to default settings
0
0
1
P4
Selection of type of inputs
1
=Probe S1
2
=Probes S1 + S2
1
1
2
P7
Temperature display mode
0
=Integers in ºC
1
=One decimal in ºC
2
=Integers in ºF
3
=One decimal in ºF
0
1
3
P8
Probe to be displayed (as per parameter P4)
0
=visualization of all the probes in sequence;
1
=Probe S1
2
=Probe S2
0
1
2
Level 2
20