background image

1763H532 Ed.02

7.6.- Alarms

The unit warns the user by displaying an on-screen message when the programmed criteria are met.

Max/Min Temperature Alarm

Shows the 

AH 

or 

AL 

message when the temperature in probe 1 reaches the value set in 

the 

A1

 (maximum temperature) or 

A2

 (low temperature) parameters.

This value can be:

Absolute (A0=1): A1/A2

 should indicate the temperature at which the alarm should 

be activated.

Relative  to  SP  (A0=0):  A1/A2

  should  indicate  the  number  of  degrees  above  or 

below  the  set  point  at  which  the  alarm  is  activated.  This 
option allows users to adjust the set point without having to 
modify the high and low alarm settings.

Parameter 

A10

 sets the differentials for both parameters (hysteresis).

 

Example

In a controller we configure the following parameters: 

SP

=2, 

A1

=10, 

A10

=2

- If A0=0 (relative to SP), the maximum temperature alarm goes off when probe 1 reaches 12 degrees 

and is disabled when it reaches 10 degrees. 

- If A0=1 (absolute), the maximum temperature alarm goes off when probe 1 reaches 10 degrees and 

is disabled when it reaches 8 degrees.

In the case of configuring the alarms in relation to the 

SP

 (

A0

=0), the value set for the 

SP

 parameter is 

taken as a reference, even though the “CHANGE SET POINT” function may have been activated.

External alarm/severe external alarm

Displays  the  message 

AE 

(external  alarm)  or 

AES 

(severe  external  alarm),  when  the  digital 

input configured as external alarm or severe external alarm is activated.
The severe external alarm also deactivates all the charges, therefore, the temperature regulation 
is stopped. When this alarm disappears the device returns to its normal operation.
At least one of the digital inputs must be configured as external alarm (

P10 

or

 P11

=2) or severe external alarm 

(

P10 

or

 P11

=3).

Defrost alarm completed by time.

Shows the 

Adt 

alarm message when a defrost terminates by time-out, if parameter 

A8

=1.

Door open alarm 

Displays the 

PAb

 message when the door stays open for a time greater than that set with parameter 

A12

. (One of 

the digital inputs must be configured as door contact (

P10 or P11=

1).

Pump down malfunction error (Stop)

Displays  the 

Pd

  message  if  a  malfunction  is  detected  when  the  installation  is  stopped 

using the pump down manoeuvre. (See p. 13).

14

Содержание PROCool AKO-17635-1

Страница 1: ...AKO 17635 1 AKO 17635 2 PROCool Electronic Panel GB 1763H532 Ed 02 User manual 1...

Страница 2: ...damage which may occur due to failure to comply with these regulations Rigorouslyfollowtheinstructionsdescribedinthismanual Inordertoextendthelifetimeofourproductstothemaximum thefollowingpointsmustbe...

Страница 3: ...only probes supplied by AKO should be used Between 40 C and 20 C if the NTC probe is extended up to 1 000 m with minimum 0 5 mm wire the maximum deviation will be 0 25 C Wire for probe extension ref...

Страница 4: ...Checks before starting the panel up Powersupplyvoltagesandfrequencieswillbetheonesthatfigureinthe Technicalspecifications section Checkthattherearenoloosepartsorforeignbodiesonconnectionsorswitchgear...

Страница 5: ...the advanced configurationmenu During configuration it allows you to scroll through the different levels or when setting a parameter tochangeitsvalue One short press displays the current set point va...

Страница 6: ...ture set in A2 has been reached p 14 Alternating with temperature External alarm activated by digital input p 14 Alternating with temperature Severe external alarm activated by digital input p 14 Alte...

Страница 7: ...escribed depends on the panel model AKO 17635 1 AKO 17635 2 Identification F1 General circuit breaker FM Operation circuit breaker FK1 Compressor motor guard condenser fan 1 depending on model K1M Com...

Страница 8: ...1 Maximum defrost duration The defrost will end after this time has elapsed since it started F3 Fan status during defrost It defines the status of the fans during defrost 0 Stopped 1 Running A1 Maximu...

Страница 9: ...n external switch configuring one of the digital inputs as Change set point P10 or P11 4 If we set the C11 parameter to 0 it can only be activated by external switch ON SP SP Dif OFF COMP C When the t...

Страница 10: ...he average performance of the last 24 hours taking into account the number of starts and stops and the average time in each state stop start C6 3 The compressor will run as scheduled in C7 ON and C8 O...

Страница 11: ...mination The defrost will terminate if The temperature programmed in parameter d4 has been reached in probe 2 Probe 2 must be activated P4 In the event of probe 2 failure defrosting will be complete o...

Страница 12: ...configuredas remotedefrost P10 P11 6 7 3 Fan control Fans are controlled with probe 2 evaporator and parameters F0 shutdown temperature and F1 Probe differential Even if probe 2 is not connected or an...

Страница 13: ...sostat is activated but it will display the Pd message after 15 minutes STARTUP When the temperature in probe 1 reaches the set point plus the differential SP C1 value the liquid solenoid opens This i...

Страница 14: ...nd is disabled when it reaches 8 degrees In the case of configuring the alarms in relation to the SP A0 0 the value set for the SP parameter is taken as a reference even though the CHANGE SET POINT fu...

Страница 15: ...er defrost A4 Delays activation of temperature alarms post defrost Delay of max min temperature alarm A5 Delays activation of maximum A1 and minimum A2 temperature alarms from the moment temperature p...

Страница 16: ...ipment to the key Connect the programming key in the parameter server connector Press the READ key on the programming key Disconnect the device programming key Transfer parameters from the key to the...

Страница 17: ...isfunctionconfiguresalltheunit sparameterstoitsdefaultvalues i e asitleavesthefactory In order to return the computer to its initial settings go to the programming menu and set parameter P3 to 1 The c...

Страница 18: ...45 C2 C4 Typeofdelayforprotectionofthecompressor Page10 0 OFF ON sincethelastdisconnection 1 OFF ON ON OFF sincethelastshut down start up 0 0 1 C5 Protectiondelaytime valueoftheoptionselectedinparame...

Страница 19: ...up Page12 0 NO Firstdefrostasperd0 1 YES Firstdefrostasperd6 0 0 1 d6 Defroststartdelayonequipmentstart up Page12 min 0 0 255 d8 Calculatedtimebetweendefrostperiod Page12 0 Totalactualtime 1 Sumoftim...

Страница 20: ...nalofthedigitalinputdisappears P10orP11 2or3 Page15 min 0 0 120 A8 Showwarningifdefrostisterminatedbytime out 0 No 1 Yes Page14 0 0 1 A10 TemperatureAlarmDifferential A1andA2 Page14 C F 0 1 1 0 20 0 A...

Страница 21: ...mumstart uptimeafterpumpdown Page13 Valuesbetween1and9secondsarenotaccepted 0 Disabled sec 0 0 120 P15 Maximumpumpdowntime Page13 0 Disabled min 0 0 15 P23 Stopevaporatorfansandcompressoronopeningdoor...

Страница 22: ...ion 1 C PrecisionoftheNTCprobeat25 C 0 4 C InputforNTCprobe AKO 14901 Maximuminputpowerintheoperation 30VA Workingambienttemperature 5 Cto40 C Storageambienttemperature 30 Cto70 C Overvoltagecategory...

Страница 23: ...ight to supply materials that might vary slightly to those described in ourTechnical Sheets Updated information is available on our website AKO ELECTROMEC NICA S A L Avda Roquetes 30 38 08812 Sant Per...

Отзывы: